Q1. At an office car park, the isolator for the charger circuit is placed behind a locked panel to stop tampering. What condition does the Code attach to this?

Show answer

Answer: C. Opening the panel must not expose parts with less than IP2X / IPXXD protection

  • A means of isolation must be readily accessible for maintenance and identified by marking or labelling.
  • It may be behind a panel or door opened by a key or tool, provided that this does not give access to equipment not protected by barriers or similar to at least IP2X / IPXXD.

This balances security against public tampering with safe access for maintenance.

Why the others are wrong:

A: the Code gives no distance; it requires ready access for maintenance and correct labelling.

B: the Code allows a key or tool held by the site; the DNO is not mentioned.

D: the Code places no such type or rating condition on the isolator.

Memory trick:

Locked panel fine, but nothing live behind it.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 89

Reg CoP 8.6.2

Q2. A single-phase 230 V charger uses open-PEN detection that monitors line-neutral voltage. The voltage drop from the supply point to the consumer unit is 2.0 V. The charger draws 32 A and the cable's voltage drop is 7.3 mV/A/m. What is the maximum cable length to the charger?

Show answer

Answer: D. About 30.8 m

  • Where open-PEN detection on line-neutral voltage is used, the voltage drop from the public supply connection to the EVSE must be less than 4 % of U0, to prevent unwanted operation.
  • 4 % of 230 V = 9.2 V; 9.2 - 2.0 = 7.2 V left for the final circuit.
  • 7.2 / (32 x 0.0073) = about 30.8 m, the circuit must be shorter than this.

The drop is measured from the supply point, so the upstream drop counts.

Why the others are wrong:

A: this uses 5 % and also ignores the 2.0 V upstream drop; the limit is less than 4 % from the supply point.

B: this uses the whole 4 % for the charger cable and ignores the 2.0 V already dropped upstream.

C: this uses a 3 % lighting limit rather than the Code's 4 % figure for open-PEN detection.

The maths

Limit: 4 % x 230 V = 9.2 V (from supply point to EVSE)
Available for final circuit: 9.2 - 2.0 = 7.2 V
Drop per metre: 32 A x 7.3 mV/A/m = 233.6 mV/m = 0.2336 V/m
Max length: 7.2 / 0.2336 = 30.8 m, so the circuit must be shorter than about 30.8 m.

Memory trick:

Open-PEN: under 4 % from the cut-out to the car.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 67

Reg CoP 6.8.3

Q3. A local authority wants to supply an 11 kW on-street charger from the MET of a PME supply. What is the usual DNO position?

Show answer

Answer: B. They refuse loads over 2 kW unless certified open-PEN detection is agreed

  • DNOs will not provide the MET of a PME supply for street furniture with loads greater than 2 kW, unless they agree to an independently certified open-PEN detection device in line with G12/4.
  • Otherwise a separate TT earthing system is often used for on-street chargers.

Some DNOs permit TN-C-S where open-PEN detection is at the charger or feeder pillar.

Why the others are wrong:

A: RCDs do not protect against the open-PEN touch voltage risk the DNO is concerned with.

C: the Code gives a 2 kW load threshold for street furniture, not a 22 kW one.

D: lamppost mounting does not change the rule; open-PEN protection also limits mounting on existing street furniture.

Memory trick:

Street load over 2 kW: no PME without a certified open-PEN.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 76

Reg CoP 7.3.3.3

Q4. Each on-street charger contains a 30 mA RCD. Which device does the Code give as an example for the feeder pillar to achieve selectivity?

Show answer

Answer: D. A 300 mA Type S RCD

  • There shall be selectivity between the RCD at or in the charging equipment and other RCDs in the installation.
  • Example: 30 mA RCD (Type A, F or B) in the charger, with a 100 mA, 300 mA or 500 mA Type S RCD in the feeder pillar.

Type S (time-delayed) with a higher rating lets the downstream 30 mA device clear first.

Why the others are wrong:

A: a more sensitive upstream device would trip before the 30 mA RCDs in the chargers.

B: the same rating and no time delay would not give selectivity with the 30 mA RCDs in the chargers.

C: without the time delay of a Type S device, selectivity would not be assured.

Memory trick:

Upstream: bigger and slower (S).

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 78

Reg CoP 7.3.5.2

Q5. An on-street installation feeds four charging points that are all expected to charge at the same time. Using the Code's guidance, what is the minimum current the installation should be able to provide?

Show answer

Answer: B. 32 A

  • Charging needs at least 6 A to start, but some vehicles will not charge at 8 A.
  • A single on-street charging point should provide at least 10 A (2.3 kW).
  • Where points may charge simultaneously, provide at least 8 x n A.
  • 8 x 4 = 32 A.

Street furniture cut-outs are typically 25 A and rated in open air, so their effective rating may be lower.

Why the others are wrong:

A: this uses 6 A per point; some vehicles will not even charge at 8 A, so 6 A per point is too low.

C: this applies the 10 A single-point figure to every point; the simultaneous figure is 8 A per point.

D: this is the typical cut-out rating in street furniture, not the minimum needed for four points.

The maths

Rule for simultaneous charging: I = 8 x n
n = 4 charging points
I = 8 x 4 = 32 A

Memory trick:

One point 10 A; many points 8 each.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 71

Reg CoP 7.1.2 NOTE 1

Q6. An extra consumer unit is needed for a new EV circuit by splitting the meter tails before the existing consumer unit. Which method does the Code accept?

Show answer

Answer: A. Terminal blocks in an insulated enclosure after a supply-side isolator

  • Tails may be split using suitable terminal blocks in insulated enclosures.
  • The split is made on the consumer's side of a supply-side isolator, fitted on the consumer's side of the fiscal meter (fit one if absent).
  • Insulation displacement connectors (vampire taps, line taps) shall not be used.

The isolator allows safe maintenance of the terminal blocks and consumer units.

Why the others are wrong:

B: these 'vampire taps' must not be used; they are intended for out-of-reach overhead line work.

C: the split must be on the consumer's side of an isolator that is itself on the consumer's side of the meter.

D: the Code calls for suitable terminal blocks in insulated enclosures, not doubling up at the main switch.

Memory trick:

Meter, isolator, then blocks: never vampire taps.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 60

Reg CoP 6.2.5