EV Charging 2921-34: Electrical requirements practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

29 of our 112 Electric Vehicle Charging Equipment Installation (2921-34) questions are on electrical requirements, about 26% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A charger contains both an overcurrent protective device and an RCD meeting Regulations 722.533.101 and 722.531.3.101 for each charging point. How may the circuit feeding the charger be treated?

Show answer

Answer: A. As a distribution circuit

  • BS 7671 effectively defines the charging point as the socket-outlet, fixed connector or tethered connector.
  • Where both overcurrent and residual current devices for each point are inside the EVSE, the supply circuit could be considered a distribution circuit.

The EVSE then contains the final circuits for its charging points.

Why the others are wrong:

B: where the EVSE contains the required protection, the supply can be treated as a distribution circuit.

C: ring circuits are not mentioned; EV charging points need dedicated supplies.

D: electrical separation needs an isolating transformer, which is not described here.

Memory trick:

Protection inside the box: the cable in is a distribution circuit.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 47

Reg CoP 5.4.2

Q2. A house on PME has full main protective bonding. Why does this bonding not protect a person standing on the drive touching a car on charge?

Show answer

Answer: C. The person is in contact with true Earth, not the bonded zone

  • Inside the building, main bonding keeps conductive parts at a similar potential, protecting occupants.
  • Outside, a person may touch parts connected to PME earth (the vehicle on charge) while standing on true Earth.
  • The bonding does nothing for that voltage difference.

This is the core reason for the extra PME rules for outdoor charging points.

Why the others are wrong:

A: in Mode 3 charging the vehicle body is connected to the cpc, which is why it can rise in voltage.

B: main bonding works independently of RCDs; the issue is the person's contact with true Earth.

D: main bonding equalises potential inside the building during faults, not only from surges.

Memory trick:

Bonding protects inside the bubble, not on the drive.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 38

Reg CoP 5.3.1

Q3. A homeowner believes the new 30 mA RCD for their charger will protect them if the supply PEN conductor breaks. What is the correct response?

Show answer

Answer: C. An RCD gives no protection against an open PEN

  • With an open PEN, all conductive parts connected to the earthing system can rise to a dangerous voltage.
  • Load current may return via the protective conductors, overheating earthing and bonding conductors.
  • The Code states plainly that an RCD will not provide any protection against these effects.

That is why Regulation 722.411.4.1 needs an electrode, an open-PEN device or separation.

Why the others are wrong:

A: no RCD type detects an open-circuit PEN conductor in the network.

B: an open PEN does not create a residual current through the RCD, so it will not operate.

D: testing confirms the RCD works, but it still cannot detect an open PEN.

Memory trick:

Broken PEN raises the earth itself: the RCD sees nothing.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 36

Reg CoP 5.3.1

Q4. A charger has an integral 30 mA RCD. Part of its supply cable is concealed in a wall at a depth of 40 mm, so the circuit itself needs 30 mA RCD protection at the consumer unit. What does the Code say about RCD selectivity in this case?

Show answer

Answer: C. Selectivity between the two RCDs may not be practicable

  • The Code expects co-ordination (selectivity) between an RCD at the charging point or in the EVSE and the protection at the origin of the circuit.
  • It accepts that this is not always practicable, for example where part of the circuit is concealed in a wall at less than 50 mm depth.

Cable buried at under 50 mm needs 30 mA protection, so both devices end up at 30 mA.

Why the others are wrong:

A: other BS 7671 requirements still apply; the Code gives this as the example where selectivity fails.

B: two 30 mA devices cannot be relied on to discriminate; this is why selectivity may not be practicable.

D: a 100 mA S-type device would not give the 30 mA protection needed for cable at less than 50 mm depth.

Memory trick:

Shallow cable, double 30 mA, no selectivity.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 50

Reg CoP 5.6.2

Q5. A rural house is fed by an overhead LV line. The owner wants to skip surge protection when the new charger is fitted. What does the Code say?

Show answer

Answer: B. Omitting it could risk life, so it should not generally be left out

  • Surge protection is required where overvoltages could cause serious injury or loss of life, or significant financial or data loss.
  • Where the building has a lightning protection system or an overhead LV supply, omitting surge protection could put life at risk, so it should not generally be omitted.
  • Installers should remind owners that EVs and chargers are expensive assets.

Type 1 SPDs are usually needed on supplies to distribution equipment for external charging points.

Why the others are wrong:

A: with an overhead LV supply, omission could risk serious injury or loss of life.

C: the charger rating does not decide this; the supply type and risk do.

D: BS 7671 requires it unless the owner accepts a tolerable risk, which is not the case here.

Memory trick:

Overhead line or lightning rod: keep the SPD.

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 52

Reg CoP 5.11.1 / Section 443

Q6. A commercial site with an EV charging installation has a PME supply whose PEN (supply neutral) conductor is 120 mm² copper. What is the minimum csa of copper main protective bonding conductor?

Show answer

Answer: D. 35 mm²

  • Under PME conditions, main bonding is sized from the supply neutral, using Table 54.8.
  • Over 95 mm² up to 150 mm² requires 35 mm² copper equivalent.
  • The absolute minimum is 10 mm², and the local DNO may require more.

Bonding must be large enough to carry diverted load current if the PEN conductor opens.

Why the others are wrong:

A: 16 mm² applies to a supply neutral over 35 mm² up to 50 mm².

B: 25 mm² applies where the supply neutral is over 50 mm² up to 95 mm².

C: 50 mm² applies only where the supply neutral exceeds 150 mm².

Memory trick:

Neutral 120 sits in the 95 to 150 band: 35 mm².

Find it in the book

IET Code of Practice for EV Charging Equipment Installation, 5th Edition, page 37

Reg CoP 5.3.1 / Table 54.8

Want 106 more EV Charging 2921-34 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.