Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. During the polarity test on a new circuit, you find the fuse in a fused connection unit is in the neutral conductor. What is the position?

Show answer

Answer: D. Non-compliant: every fuse must be in the line conductor only

  • Regulation 643.6: verify that every fuse and single-pole control and protective device is connected in the line conductor only.
  • A fuse in the neutral could leave the appliance live with the fuse blown.

Correct the connections and retest.

Why the others are wrong:

A: RCD protection does not change the polarity requirement.

B: BS 7671 requires every fuse to be in the line conductor only.

C: fuses and single-pole protective devices must also be in the line.

Memory trick:

Fuses and single-pole switches live on the line.

Find it in the book

BS 7671:2018+A4:2026, page 250

Reg 643.6

Q2. On a new schedule of test results, a ring final circuit on a 32 A Type B circuit-breaker shows a measured Zs of 1.42 Ω. Table 41.3 gives 1.37 Ω. What is the correct conclusion?

Show answer

Answer: D. It fails outright and must be investigated

  • Table 41.3, 32 A Type B: 1.37 Ω
  • Measured 1.42 Ω is above it even at room temperature

A high reading on a ring often points to a poor joint or interconnection; find and correct it, then retest.

Why the others are wrong:

A: the halving is already in the measured value; the limit still applies.

B: there is no tolerance; 1.42 Ω is above the maximum.

C: the 0.8 rule makes the limit stricter (1.10 Ω), not looser.

Memory trick:

Above the table cold means it is worse hot.

Find it in the book

BS 7671:2018+A4:2026, page 75

Reg Table 41.3; 643.7.3

Q3. A new installation with three final circuits reads 40 MΩ when tested as a whole. Tested separately, circuit 1 reads 100 MΩ and circuit 2 reads 200 MΩ. What is circuit 3's insulation resistance?

Show answer

Answer: A. 100 MΩ

  • Parallel: 1/Rtotal = 1/R1 + 1/R2 + 1/R3.
  • 1/R3 = 1/40 - 1/100 - 1/200 = 0.025 - 0.010 - 0.005 = 0.010.
  • R3 = 100 MΩ.

None of the circuits is low; the whole reading is lower simply because they are in parallel.

Why the others are wrong:

B: this subtracts the readings directly; parallel values combine as reciprocals.

C: this adds circuits 1 and 2, which is not how parallel resistance works.

D: this adds all three figures; the whole reading is lower than any single circuit.

The maths

  1. 1/40 = 0.025
  2. 1/100 = 0.010 and 1/200 = 0.005
  3. 1/R3 = 0.025 - 0.010 - 0.005 = 0.010
  4. R3 = 1 / 0.010 = 100 MΩ

Memory trick:

Work in reciprocals: 1 over each, then flip back.

Find it in the book

IET Guidance Note 3 (2022 edition), page 67

Reg GN3 2.6.7

Q4. A sub-board is fed from the origin where Ze is 0.22 Ω. The submain (R1 + R2) is 0.09 Ω. A final circuit from the sub-board on a 16 A Type C circuit-breaker has (R1 + R2) of 0.88 Ω. Table 41.3 gives 1.37 Ω. What is the position?

Show answer

Answer: B. 1.19 Ω: over the 1.10 Ω rule of thumb, so check further

  • Zdb = 0.22 + 0.09 = 0.31 Ω
  • Zs = 0.31 + 0.88 = 1.19 Ω
  • 0.8 x 1.37 = 1.10 Ω

The reading fails the quick rule of thumb but is under the table value, so a more exact assessment (for example the temperature-corrected values in GN3 Appendix A, or the designer's figures) is needed before deciding.

Why the others are wrong:

A: this leaves out the submain resistance; Zdb must include it.

C: comparing a measured value directly with the design figure ignores temperature rise.

D: it is still under the table value, so a more exact assessment is the next step, not an immediate verdict that the device must change.

The maths

Step 1: Zdb = 0.22 + 0.09 = 0.31 Ω
Step 2: Zs = 0.31 + 0.88 = 1.19 Ω
Step 3: 0.8 x 1.37 = 1.096 Ω
Step 4: 1.19 is above 1.10 but below 1.37, so check further.

Memory trick:

Over 80 % but under 100 %: do the proper sums.

Find it in the book

IET Guidance Note 3 (2022 edition), page 86

Reg Table 41.3; GN3 2.6.15, A2

Q5. Step 1 on a new ring in 2.5 mm²/1.5 mm² twin and earth gives r1 = 0.48 Ω, rn = 0.49 Ω and r2 = 0.80 Ω. What should you do next?

Show answer

Answer: A. Accept step 1 and go on to step 2

  • r1 and rn should be about the same (0.48 and 0.49 Ω).
  • r2 should be 1.67 x r1: 0.48 x 1.67 = 0.80 Ω, which matches.

Step 1 is consistent, so carry on to the step 2 cross-connection.

Why the others are wrong:

B: a higher r2 is expected because the cpc is smaller; 0.48 x 1.67 = 0.80.

C: a 0.01 Ω difference is within normal measurement variation.

D: r2 is exactly what the csa ratio predicts, so nothing suggests damage.

The maths

  1. Check r1 against rn: 0.48 vs 0.49, same order
  2. Expected r2 = 0.48 x 1.67 = 0.80 Ω
  3. Measured r2 = 0.80 Ω, matches

Memory trick:

L equals N, cpc is 1.67 times: all good, move on.

Find it in the book

IET Guidance Note 3 (2022 edition), page 62

Reg 643.2.1; GN3 2.6.6

Q6. On the A4 Schedule of Inspections, confirming that pressing the integral test button causes the RCD to trip is listed under which regulation?

Show answer

Answer: C. 643.10, as a functional check

  • 643.10: where fault or additional protection is by an RCD, the effectiveness of any test facility in the device shall be verified
  • The inspection schedule item cites 643.10 as a functional check

The instrument trip test and the test button check are separate items.

Why the others are wrong:

A: insulation testing is done dead and does not prove the test button.

B: loop impedance testing does not involve the test button.

D: voltage drop has nothing to do with the RCD test facility.

Memory trick:

Pressing buttons is functional testing.

Find it in the book

BS 7671:2018+A4:2026, page 252

Reg 643.10; Appendix 6 inspection schedule 7.13