2392-10: Safe isolation and test instruments practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

13 of our 100 Fundamental Inspection, Testing and Initial Verification (2392-10) questions are on safe isolation and test instruments, about 13% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our safe isolation and test instruments questions test most often. Know where these are in your book before the exam.

  • 537.1 · 1 questions
  • 537.2 · 1 questions
  • 643.1 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Before testing, you notice the outer insulation of a test lead is split near the probe, exposing the inner core. What should you do?

Show answer

Answer: C. Withdraw the lead and use one in good order

  • GN3 1.1(d): check that test leads, probes and clips are in good order, clean and have no cracked or broken insulation, following GS38.
  • GN3 4.1: an instrument's internal protection does not extend to the probes and leads.

A damaged lead is replaced, not patched.

Why the others are wrong:

A: insulation tests apply 500 V, and live tests may follow, so a damaged lead is unsafe.

B: leads must have no cracked or broken insulation; tape is not a proper repair.

D: instrument protection does not extend to the leads and probes.

Memory trick:

Damaged lead? Bin it, don't bodge it.

Find it in the book

IET Guidance Note 3 (2022 edition), page 14

Reg GN3 1.1 (d); GS38

Q2. A factory manager is bringing in a contractor to carry out testing. Which HSE guidance does GN3 say recommends that managers set up, or check that contractors have, a system of rules and procedures for electrical work?

Show answer

Answer: A. HSG85, Electricity at work: Safe working practices

  • GN3 1.1: HSG85, Electricity at work: Safe working practices, recommends managers establish a system of rules and procedures wherever electrical work is carried out, or ensure contractors have appropriate ones.
  • GS38 covers test equipment; HSR25 covers the EAWR, including live and dead working.

Safe testing starts with an agreed safe system of work.

Why the others are wrong:

B: GS38 covers test equipment, leads and probes, not management rules.

C: GN3 cites HSR25 for live and dead working, not for this recommendation.

D: BS 7909 covers temporary power for events.

Memory trick:

HSG85: the rulebook for safe working practices.

Find it in the book

IET Guidance Note 3 (2022 edition), page 13

Reg GN3 1.1

Q3. A control panel contains live parts fed from two separate supplies, and there is no interlock that isolates both. What must be provided?

Show answer

Answer: B. A durable warning notice to isolate all the supplies before access

  • Regulation 537.1.2: where equipment or an enclosure has live parts connected to more than one supply, a durable warning notice must be placed so that anyone gaining access is warned to isolate those parts from the various supplies.
  • The notice is not needed if an interlocking arrangement isolates all the circuits concerned.

Opening the main isolator may leave the panel live from the second source.

Why the others are wrong:

A: locking one supply does nothing about the second supply.

C: RCDs do not warn people about multiple sources before they gain access.

D: maximum demand does not warn of the need to isolate both supplies.

Memory trick:

Two supplies in one box? Warn people to kill both.

Find it in the book

BS 7671:2018+A4:2026, page 194

Reg 537.1.2

Q4. A thermal imaging check has been carried out on a distribution board with its cover removed while live. What must be done before leaving it?

Show answer

Answer: B. Replace all guards and barriers, and close and secure covers

  • GN3 4.9: people carrying out thermographic surveys must ensure all protective measures affected by their actions are fully reinstated.
  • All guards and barriers must be replaced, and panel doors, lids and covers closed and secured after the inspection.
  • They must also keep the maximum possible distance from live parts and control the area.

Whatever you open for testing, you put back exactly as safe as you found it.

Why the others are wrong:

A: all protective measures affected must be fully reinstated.

C: guards and covers must be put back, not just labelled.

D: the inspector must reinstate the protective measures disturbed.

Memory trick:

Leave it as safe as you found it: covers on, doors shut.

Find it in the book

IET Guidance Note 3 (2022 edition), page 147

Reg GN3 4.9; EAWR Reg 14

Q5. You are about to disconnect the earthing conductor from the MET to measure Ze at a new consumer unit. What state should the main switch be in, as shown in GN3's example?

Show answer

Answer: A. Off, and secured with a safety locking device

  • GN3: Ze is measured between the supply line conductor and the means of earthing with the main switch open (or all circuits isolated), and the means of earthing disconnected from the MET.
  • The example figure shows the main switch off, secured by a safety locking device.
  • The earth must be reconnected before the installation is energized.

With the earth removed, nobody must be able to switch the installation back on.

Why the others are wrong:

B: the main switch is off and the means of earthing disconnected to remove parallel paths.

C: GN3's example shows the main switch secured by a safety locking device.

D: removal is not required; it is switched off and locked.

Memory trick:

Earth off? Main switch off and locked.

Find it in the book

IET Guidance Note 3 (2022 edition), page 87

Reg GN3 2.6.15 (Ze measurement)

Q6. An electrician wants to use a general-purpose meter that is not made to BS EN 61557 for some verification tests. What does BS 7671 require of it?

Show answer

Answer: C. No lesser performance and safety than BS EN 61557 equipment

  • Regulation 643.1: measuring instruments, monitoring equipment and methods shall be chosen in accordance with the relevant parts of BS EN 61557.
  • If other measuring equipment is used, it shall provide no lesser degree of performance and safety.

The standard sets the bar; anything else must clear the same bar.

Why the others are wrong:

A: the requirement is about performance and safety, not limiting it to dead tests.

B: BS 7671 sets no calibration interval for such equipment.

D: other equipment is allowed if it gives no lesser performance and safety.

Memory trick:

Not 61557? Then at least as good and as safe.

Find it in the book

BS 7671:2018+A4:2026, page 248

Reg 643.1