Q1. A new electric shower circuit in a bathroom is protected by a 40 A circuit-breaker only, with no RCD. What should the inspector record?
Show answer
Answer: A. A defect, as it needs 30 mA RCD protection
- Regulation 701.411.3.3: additional protection by RCD(s) to Regulation 415.1.1 is needed for all LV circuits serving the location, and for circuits passing through zones 1 and 2.
- The A4:2026 checklist item 12.1 asks for RCD protection not exceeding 30 mA for all LV circuits in the location.
The shower circuit must be given 30 mA RCD protection, for example by an RCBO.
Why the others are wrong:
B: the bathroom rule covers all LV circuits serving the location, fixed or not.
C: bonding does not replace the requirement for additional protection by RCD.
D: the bath or shower location has its own requirement covering every LV circuit.
Memory trick:
Bathroom circuit? 30 mA RCD, no exceptions for LV.
Find it in the book
BS 7671:2018+A4:2026, page 258