2392-10: Inspection practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

27 of our 100 Fundamental Inspection, Testing and Initial Verification (2392-10) questions are on inspection, about 27% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our inspection questions test most often. Know where these are in your book before the exam.

  • 514.4 · 3 questions
  • 411.3 · 2 questions
  • 514.12 · 2 questions
  • 527.2 · 2 questions
  • 642.2 · 2 questions
  • 701.512 · 2 questions
  • 421.1 · 1 questions
  • 462.1 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A new electric shower circuit in a bathroom is protected by a 40 A circuit-breaker only, with no RCD. What should the inspector record?

Show answer

Answer: A. A defect, as it needs 30 mA RCD protection

  • Regulation 701.411.3.3: additional protection by RCD(s) to Regulation 415.1.1 is needed for all LV circuits serving the location, and for circuits passing through zones 1 and 2.
  • The A4:2026 checklist item 12.1 asks for RCD protection not exceeding 30 mA for all LV circuits in the location.

The shower circuit must be given 30 mA RCD protection, for example by an RCBO.

Why the others are wrong:

B: the bathroom rule covers all LV circuits serving the location, fixed or not.

C: bonding does not replace the requirement for additional protection by RCD.

D: the bath or shower location has its own requirement covering every LV circuit.

Memory trick:

Bathroom circuit? 30 mA RCD, no exceptions for LV.

Find it in the book

BS 7671:2018+A4:2026, page 258

Reg 701.411.3.3

Q2. A standard indoor IP20 socket-outlet has been fitted on the outside wall of a new house, with no weatherproof cover. Which inspection item does this fail?

Show answer

Answer: D. Equipment suits the external influences at its location

  • Regulation 512.2 and the GN3 checklist: equipment must suit its environment, including water, dust, temperature and impact.
  • The checklist also asks for a suitable degree of protection (IP code) for the external influences.

IP20 gives no protection against water, so it is not suitable outdoors.

Why the others are wrong:

A: the schedule does not deal with weather protection.

B: labelling does not deal with the effects of rain and dust.

C: this is about the main switch, not the outdoor socket.

Memory trick:

Outdoors means weather: check the IP code.

Find it in the book

IET Guidance Note 3 (2022 edition), page 41

Reg 512.2

Q3. Which of these checks is part of the inspection, rather than the testing, of a new installation?

Show answer

Answer: A. Checking conductors are tight with no stray strands

  • Inspection is an examination of the installation: things are looked at and checked, not measured with instruments.
  • GN3 checklist items include all connections secure and terminals tight and containing all strands.

Tests use instruments to measure values; inspection confirms things are correctly selected, erected and undamaged.

Why the others are wrong:

B: this is a continuity test using a low-resistance ohmmeter.

C: this is an insulation resistance test.

D: this is an RCD test using an instrument.

Memory trick:

Inspection: eyes and hands. Testing: instruments and numbers.

Find it in the book

IET Guidance Note 3 (2022 edition), page 48

Reg 642.2; GN3 2.5

Q4. A new extension is being wired. At what stages does BS 7671 require it to be inspected and tested?

Show answer

Answer: A. During erection and on completion, before it is put into service

  • Regulation 641.1: every installation is inspected and tested during erection and on completion before being put into service.
  • The aim is to verify, so far as reasonably practicable, that BS 7671 has been met.

Initial verification is not a one-off visit at the end. Some items can only be seen while the work is still open.

Why the others are wrong:

B: the installation must be verified before it is put into service, and inspection also runs during erection.

C: periodic inspection is a separate later activity; initial verification comes first.

D: the duty comes from BS 7671 itself, not from a request by building control.

Memory trick:

Inspect as you build, verify before you energise for use.

Find it in the book

BS 7671:2018+A4:2026, page 247

Reg 641.1

Q5. The design schedule shows a B16 circuit-breaker for an immersion heater circuit. During inspection you find a B32 has been fitted. What should you conclude?

Show answer

Answer: D. A defect, as the wrong device has been fitted

  • GN3 checklist: correct fuses or circuit-breakers are installed (Sections 531 and 533).
  • The inspector checks what is installed against the design information.

A 32 A device on a circuit designed for 16 A may let the cable overheat before it trips.

Why the others are wrong:

A: the curve may match but the rating does not.

B: a larger device may not protect the cable and does not match the design.

C: an RCD test does not check the overcurrent rating chosen by the designer.

Memory trick:

Check the breaker against the design, rating and type.

Find it in the book

IET Guidance Note 3 (2022 edition), page 47

Reg GN3 checklist (x); Section 533

Q6. At a new consumer unit, a spare green-and-yellow core has been sleeved brown and used as a line conductor. What should the inspector conclude?

Show answer

Answer: B. Non-compliant, as green-and-yellow is only for protective conductors

  • Regulation 514.4.2: green-and-yellow is used exclusively for protective conductors.
  • Cores that are green-and-yellow throughout their length shall not be overmarked at terminations (other than the PEN case).

Anyone seeing green-and-yellow will assume it is safe to touch. Using it as a line is dangerous.

Why the others are wrong:

A: green-and-yellow cores must not be overmarked to change their function.

C: no circuit type allows green-and-yellow to be used as a line.

D: recording a misuse does not make it compliant.

Memory trick:

Green-and-yellow means earth, full stop.

Find it in the book

BS 7671:2018+A4:2026, page 141

Reg 514.4.2

Want 94 more 2392-10 questions? Start a free timed mock.