Q1. For which of these installations must you NOT include any adventitious air allowance when sizing ventilation?
Show answer
Answer: A. A boiler installed in a compartment
- Adventitious air is not taken into account for:
- flueless appliances
- appliances in compartments
- DFE gas appliances
Compartments use the total maximum rated heat input with no deduction.
Why the others are wrong:
B: an open-flued appliance in a room does get the first 7kW allowance.
C: adventitious air is relied on here; no vent is normally needed.
D: one appliance in a multi-appliance room still gets the allowance.
Memory trick:
Flueless, compartment, DFE: no free air for them.
Find it in the book
CORGI GID1, 10th Edition, Volume 1, page 85