ACS CCN1: Combustion and carbon monoxide practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

34 of our 270 ACS CCN1 Core Domestic Gas Safety (ACS-CCN1) questions are on combustion and carbon monoxide, about 13% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. An open-flued appliance is burning air that is short of oxygen because its own products are spilling back into the room. What is this condition called?

Show answer

Answer: B. Vitiation

  • Vitiation: combustion air is deficient of oxygen, possibly due to spillage from a faulty flue.
  • Causes include poor ventilation, incorrect flue design or a damaged or blocked flue.
  • Signs: flame lift off, soot staining.

Vitiated air leads to incomplete combustion and CO.

Why the others are wrong:

A: impingement is flame contact with a cold surface such as the heat exchanger.

C: aeration refers to primary air adjustment at the burner.

D: light back is the flame burning back into the mixing tube.

Memory trick:

Vitiated = Very short of oxygen.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 46

Reg GID1 Part 3, Table 3.2

Q2. A kitchen measures 4 m x 3 m x 2.5 m high. Assuming escaping natural gas mixes evenly with the air, roughly how much gas would bring the room to its lower flammability limit?

Show answer

Answer: B. 1.5 m3

  • Natural gas burns between 5% and 15% gas in air.
  • The lowest figure, 5%, is the Lower Flammability Limit (LFL).
  • Room volume = 4 x 3 x 2.5 = 30 m3; 5% of 30 = 1.5 m3.

Mixtures between 5% and 6% are hard to ignite, but anything inside the 5% to 15% range can burn.

Why the others are wrong:

A: this uses the upper flammability limit of 15%, not the lower limit.

C: this uses 2%, which is the lower limit for propane and butane.

D: this uses 10%, which is the upper limit for propane.

The maths

Room volume = 4 x 3 x 2.5 = 30 m3
LFL for natural gas = 5%
Gas needed = 30 x 0.05 = 1.5 m3

Memory trick:

NG: 5 to 15. LPG: starts at 2.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 43

Reg GID1 Part 3, Flammability limits

Q3. Under BS EN 50291, how quickly must a CO alarm sound when exposed to 300 ppm of CO?

Show answer

Answer: B. Within 3 minutes

  • 50 ppm: alarm between 60 and 90 minutes.
  • 100 ppm: alarm between 10 and 40 minutes.
  • 300 ppm: alarm within 3 minutes.

Higher concentrations need a faster response because effects arrive sooner.

Why the others are wrong:

A: this is the response required at 100 ppm.

C: this is the response required at 50 ppm.

D: the standard gives 3 minutes at 300 ppm, not 30 seconds.

Memory trick:

50: an hour plus, 100: half hour-ish, 300: three minutes.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 76

Reg GID1 Part 3, CO alarm levels, BS EN 50291

Q4. Which standard is the current build standard for portable electronic combustion gas analysers (ECGAs)?

Show answer

Answer: B. BS EN 50379-3

  • BS EN 50379-3 replaced BS 7927 as the build standard for ECGAs.
  • BS 7967 is the code of practice on how to use them.

The analyser should conform to BS EN 50379-3 and hold current calibration.

Why the others are wrong:

A: BS 7967 is the guide to using analysers, not the build standard.

C: this is the standard for carbon monoxide alarms.

D: this is the standard for domestic gas detector alarms.

Memory trick:

Build = 50379; use = 7967.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 55

Reg GID1 Part 3, Industry standards for flue gas analysers

Q5. While sampling a flue, the CO reading is climbing fast and will clearly go past 2000 ppm. What should you do?

Show answer

Answer: C. Remove the probe, turn off the appliance and purge the analyser in outside air

  • If CO will clearly exceed 2000 ppm: remove the probe from the flue and turn off the appliance.
  • Detach the probe and purge it in outside air until CO and CO2 read zero.

Prolonged high CO exposure shortens sensor life and lengthens purging.

Why the others are wrong:

A: the instruction is to remove the probe and turn the appliance off.

B: high CO exposure damages the sensor and the appliance must be turned off.

D: the probe must be removed and purged until CO and CO2 return to zero.

Memory trick:

Over 2000? Probe out, gas off.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 62

Reg GID1 Part 3, Checking combustion performance

Q6. Commissioning a condensing boiler at maximum rate, with no specific figures in the instructions, you read 280 ppm CO and 6.0% CO2. What is the outcome?

Show answer

Answer: C. Ratio is about 0.0047, above 0.0040, so the boiler is not satisfactory

  • Default commissioning action levels: CO at or below 350 ppm and ratio at or below 0.0040.
  • Ratio = 280 / (6.0 x 10,000) = 0.0047, which exceeds 0.0040.
  • Do not adjust the air/gas ratio valve without contacting the manufacturer; follow the flowchart and GIUSP.

Both values must pass at maximum and minimum rate.

Why the others are wrong:

A: the ratio has been calculated ten times too high.

B: both CO and the combustion ratio must be within their action levels.

D: the commissioning action level is 0.0040, not the 0.008 servicing figure.

The maths

CO2 = 6.0% x 10,000 = 60,000
Ratio = 280 / 60,000 = 0.00467
0.00467 > 0.0040 action level, so not satisfactory even though CO (280) is below 350 ppm

Memory trick:

Commissioning: 350 ppm and 0.004, both must pass.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 63

Reg GID1 Part 3, Commissioning action levels

Want 264 more ACS CCN1 questions? Start a free timed mock.