ACS CCN1: Pipework, meters, regulators and emergency controls practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

42 of our 270 ACS CCN1 Core Domestic Gas Safety (ACS-CCN1) questions are on pipework, meters, regulators and emergency controls, about 16% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. You are making a screwed steel joint on a natural gas installation using PTFE tape. Which method is correct?

Show answer

Answer: D. 50% overlap, wound against the thread, no other compound

  • Use PTFE tape of the correct type, suitable for NG and LPG (normally to BS EN 751-3).
  • Wind with a 50% overlap to give a double cover, starting from the thread end, counter to the thread form.
  • Do not use PTFE with other jointing compounds.

Winding the wrong way lets the tape unravel as the joint is tightened.

Why the others are wrong:

A: compound and tape go on the external thread of the pipe or fitting.

B: PTFE must not be used with other jointing compounds and is wound against the thread.

C: it is wound counter to the thread, and hemp is not combined with PTFE tape.

Memory trick:

Half over, wrong way round, nothing else on top.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 124

Reg GID1 Part 5, PTFE tape

Q2. A vertical gas pipe is to be boxed in behind plasterboard fixed on battens. The pipe ends up 40 mm from the face of the plasterboard. What extra protection is needed?

Show answer

Answer: B. A 1 mm thick steel plate over the pipe

  • On battens, rising pipes are surface mounted and corrosion protected, with a batten closely fitted either side.
  • Add a 1 mm thick steel plate if the pipe is within 50 mm of the plasterboard face.
  • Seal joints between batten and wall with mastic so gas cannot track round the batten.

This protects the pipe from screws and nails driven into the board later.

Why the others are wrong:

A: a soft wrap does not stop screws or nails; the requirement within 50 mm of the board face is a 1 mm steel plate.

C: the requirement for pipes within 50 mm of the board face is a steel protection plate, not a sleeve.

D: being within 50 mm of the face is exactly when the steel plate is required.

Memory trick:

Inside 50, add a steel plate of 1.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 145

Reg GID1 Part 5, Dry lined walls

Q3. On an NG meter you read 24 mbar with nothing running. With the boiler at full load and other appliances at 50% you read 19.2 mbar after one minute. What is the correct conclusion?

Show answer

Answer: A. It is satisfactory, no report is needed

  • With no gas flowing you read standing pressure, which normally exceeds 21 mbar; do not confuse it with operating pressure.
  • At high operating load, after a one minute stabilisation period, the outlet pressure must be not less than 18.5 mbar and not exceeding 23 mbar.
  • 19.2 mbar is inside the range, so no action is needed.

Only a reading outside the range is reported to the emergency service provider.

Why the others are wrong:

B: the 18.5 to 23 mbar range applies to the operating pressure under load, not the standing pressure.

C: 21 mbar is nominal; under high load anything from 18.5 to 23 mbar is acceptable.

D: only the GT or their approved agents may adjust the sealed meter regulator.

Memory trick:

Loaded, wait a minute, between 18.5 and 23.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 181

Reg GID1 Part 7, Checking the operating pressure

Q4. To check a meter regulator in a house with a combination boiler and a four burner hob, how should you create the high operating load?

Show answer

Answer: A. All hot taps at full flow, two hob burners lit

  • High operating load: the highest output appliance at its maximum load (for a combi, all hot taps at full flow).
  • Other appliances at 50% load, for example two of four hob burners lit.
  • Then read the meter outlet after one minute.

This simulates a period of high demand for the whole installation.

Why the others are wrong:

B: the highest output appliance, the boiler, must run at maximum load.

C: the boiler must be at maximum load; on a combi that is hot water demand.

D: the combi needs all hot taps at full flow, other appliances at only 50% load.

Memory trick:

Big one flat out, the rest at half.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 182

Reg GID1 Part 7, High operating load

Q5. You are fitting an AECV where the supply enters a flat fed from a remote meter. What is an appropriate height for it?

Show answer

Answer: C. Between 450 mm and 1450 mm above the floor

  • AECVs are needed where gas enters a dwelling fed from a remote meter, where supply passes to a separate building not under one responsible person, and at each dwelling in a building of flats.
  • An appropriate height is 450 mm to 1450 mm above floor level.

That keeps the valve easy to reach for any occupant.

Why the others are wrong:

A: this is above the appropriate range.

B: this is lower than the appropriate range.

D: the 2 m figure relates to notices about ECV position, not AECV height.

Memory trick:

AECV between knee and shoulder: 450 to 1450.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 196

Reg GID1 Part 9, Additional ECVs

Q6. A gas transporter fits an excess flow valve for a typical 6 m3/hr domestic meter. What trip range would normally be expected?

Show answer

Answer: B. 7.8 to 8.7 m3/hr

  • An EFV shuts off if downstream escaping gas exceeds a pre-set rate, a sensible margin above maximum demand or meter rating.
  • For a 6 m3/hr meter, a trip range of 7.8 to 8.7 m3/hr would be expected.
  • It protects against catastrophic failure such as meter theft, damage, vandalism or fire.

Leaks smaller than the trip setting are not protected against.

Why the others are wrong:

A: that is below the meter's capacity and would trip in normal use.

C: the trip is set a sensible margin above the meter rating, not at it.

D: this is higher than the typical range given.

Memory trick:

6 meter, trip at about 8.

Find it in the book

CORGI GID1, 10th Edition, Volume 1, page 198

Reg GID1 Part 9, Excess flow valve

Want 264 more ACS CCN1 questions? Start a free timed mock.