40 of our 270 ACS CCN1 Core Domestic Gas Safety (ACS-CCN1) questions are on tightness testing and purging, about 15% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. After purging you find a newly fitted appliance that has not been commissioned. What must you do?

Show answer

Answer: C. Disconnect or seal it off and label it, or commission it

  • Where an appliance is found that has not been commissioned, it must be either:
    • disconnected from the gas supply or sealed off with an appropriate fitting and labelled as not commissioned, or
    • commissioned.

An uncommissioned appliance must never be left live and unlabelled.

Why the others are wrong:

A: closing a valve alone is not one of the stated options.

B: it must be disconnected and labelled, or commissioned.

D: the appliance must be dealt with, not just recorded.

Memory trick:

Not commissioned? Cap and tag it, or commission it.

Find it in the book

CORGI TTP1 Tightness Testing and Purging, 5th Edition, page 28

Reg TTP1 Purging procedure

Q2. When surveying an installation you find a section of inaccessible pipework of unknown length and mixed sizes. What should you assume for the IV calculation?

Show answer

Answer: D. The largest visible diameter for the maximum length

  • For inaccessible pipework of different sizes and unknown length, always assume the largest visible diameter for the maximum length.
  • This gives a worst case (largest) IV.

Overestimating the volume keeps the permitted drop and purge volume on the safe side.

Why the others are wrong:

A: the 10% allowance is for fittings, not hidden pipe.

B: this would underestimate the volume, which is unsafe.

C: averaging is not the method given and may underestimate.

Memory trick:

Can't see it? Assume the biggest pipe, longest run.

Find it in the book

CORGI TTP1 Tightness Testing and Purging, 5th Edition, page 9

Reg TTP1 Calculating installation volume

Q3. A water 'U' gauge cannot be zeroed. One leg reads 11.5 mbar and the other 8.5 mbar against the scale. What is the correct pressure reading?

Show answer

Answer: A. 10 mbar

  • If the water gauge cannot be zeroed, record the readings of the two meniscuses, add them together and divide by two.
  • (11.5 + 8.5) / 2 = 10 mbar.

Averaging the two legs cancels out the zero offset.

Why the others are wrong:

B: that is the sum of the two legs, which has not been halved.

C: that is the difference between the legs, which is not the method given.

D: reading one leg only ignores the offset from zero.

The maths

Step 1: add the two leg readings: 11.5 + 8.5 = 20 mbar.
Step 2: divide by two: 20 / 2 = 10 mbar.

Memory trick:

Not zeroed? Add both legs, then halve.

Find it in the book

CORGI TTP1 Tightness Testing and Purging, 5th Edition, page 7

Reg TTP1 Pressure gauges

Q4. You are testing new pipework with air and no meter fitted. How is the gauge connected and the air introduced?

Show answer

Answer: D. Via a test tee: gauge on one branch, air through the valved branch

  • A zeroed gauge is connected to one branch of a test tee; the other end of the tee is valved and used to introduce air.
  • Raise to 20 to 21 mbar, turn off the valved branch, allow 1 minute to stabilise, then test for 2 minutes.
  • There should be no perceptible drop.

It is good practice to label the pipework as having passed a test using air only.

Why the others are wrong:

A: there is no gas supply involved in an air test.

B: there is no meter fitted in this procedure.

C: the gauge and air inlet are on separate branches.

Memory trick:

Tee off: gauge on one leg, air on the valved leg.

Find it in the book

CORGI TTP1 Tightness Testing and Purging, 5th Edition, page 12

Reg TTP1 Testing new pipework using air

Q5. Before extending an existing installation you test it and record a permissible drop of 2 mbar. After connecting the extension, the retest shows 2.5 mbar. What is the result?

Show answer

Answer: C. Fail, as the drop is greater than that recorded before the work

  • Test the complete existing installation before work and record any permissible drop.
  • After connecting the extension, retest the complete installation.
  • Any drop greater than the one recorded beforehand is not acceptable: the test has failed.
  • There should be no smell of gas.

The extra drop can only have come from the new work.

Why the others are wrong:

A: the guidance compares against the recorded drop, not gauge accuracy.

B: any drop greater than the earlier recorded one is unacceptable.

D: the complete installation must be retested and this one has failed.

Memory trick:

Extension test: the 'before' drop is the ceiling.

Find it in the book

CORGI TTP1 Tightness Testing and Purging, 5th Edition, page 24

Reg TTP1 Connecting extensions

Q6. An existing installation has an E6 electronic meter and 6 m of 22 mm copper. Fittings volume is unknown. What is the maximum permissible pressure drop?

Show answer

Answer: B. 8 mbar

  • E6 meter volume = 0.0024 m3; 22 mm copper = 0.00032 m3/m.
  • IVp = 6 x 0.00032 = 0.00192 m3; IVf = 0.000192 m3.
  • IV = 0.004512 m3, which is 0.005 m3 or less: 8 mbar.

The E6's small internal volume puts short installations in the most generous band.

Why the others are wrong:

A: that applies above 0.005 m3; this IV is just under it.

C: that applies to IVs over 0.010 m3.

D: 1 mbar is the smallest limit, for IVs over 0.015 m3.

The maths

IVm = 0.0024 m3 (E6)
IVp = 6 x 0.00032 = 0.00192 m3
IVf = 0.1 x 0.00192 = 0.000192 m3
IV = 0.0024 + 0.00192 + 0.000192 = 0.004512 m3
Table 1: 0.005 m3 or less = 8 mbar

Memory trick:

Small E6, short run: biggest allowance.

Find it in the book

CORGI TTP1 Tightness Testing and Purging, 5th Edition, page 6

Reg TTP1 Calculating IV; Tables 1 to 3

Want 264 more ACS CCN1 questions? Start a free timed mock.