Carbon monoxide alarms under Part J: when, which type and where

Updated 2 November 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

Under Approved Document J (2010 edition with the 2022 amendments), fitting a new or replacement fixed solid fuel, gas or oil appliance in a dwelling means fitting a carbon monoxide alarm in the same room. Gas appliances used only for cooking are excluded. The alarm should meet BS EN 50291-1:2018 and either have a battery that lasts its whole working life or be a hard-wired Type A mains alarm with a sensor failure warning. Fit it on the ceiling at least 300mm from any wall, or high on a wall but not within 150mm of the ceiling, and 1m to 3m horizontally from the appliance.

When an alarm is needed

Requirement J3 covers warning of the release of carbon monoxide. The guidance applies whenever a new or replacement fixed combustion appliance goes into a dwelling:

  • Solid fuel appliances: paragraph 2.34 (since the 2010 edition)
  • Gas appliances, except those used solely for cooking: paragraph 3.43 (added by the 2022 amendments)
  • Oil appliances: paragraph 4.30 (added by the 2022 amendments)

Which alarm

The alarm should comply with BS EN 50291-1:2018, be powered by a battery designed to last the working life of the alarm, and warn the user when that working life is nearly over. A mains-powered Type A alarm to the same standard can be used instead, but only with fixed wiring (not a plug-in) and with a sensor failure warning device. Type A alarms have an output that can trigger other devices, such as remote alarms or specialist alarms for older or disabled people.

Where to put it

The alarm goes in the same room as the appliance.

PositionRule
On the ceilingAt least 300mm from any wall
On a wallAs high as possible, above any doors and windows, but not within 150mm of the ceiling
Distance from the applianceBetween 1m and 3m horizontally

An alarm is not a substitute

Approved Document J is clear that a carbon monoxide alarm doesn't replace correct installation and regular servicing of the appliance. More installation advice is in BS EN 50292 and the alarm manufacturer's instructions.

Official sources

Practise for it

Test yourself with a free timed mock, with every answer explained.

Start a free mock

Frequently asked questions

Do I need a CO alarm when I replace a boiler?

Yes. Since the 2022 amendments to Approved Document J, a new or replacement fixed gas or oil appliance in a dwelling needs a carbon monoxide alarm in the same room. Gas cookers are excluded.

How far should a CO alarm be from a boiler or stove?

Between 1m and 3m horizontally from the appliance, in the same room.

Can a CO alarm go on the wall?

Yes, as high up as possible and above any doors and windows, but not within 150mm of the ceiling. On the ceiling, it should be at least 300mm from any wall.

Can I use a plug-in CO alarm?

Not to meet Part J. It should be a battery alarm designed to last its working life, or a hard-wired mains Type A alarm with a sensor failure warning.

Related

Sources: Approved Document J: Combustion appliances and fuel storage systems, 2010 edition incorporating 2010, 2013 and 2022 amendments (gov.uk). This guide paraphrases the rules for revision; always work from the current official documents.