Part L rules for boilers and heating systems: what installers must meet

Updated 2 November 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

When you fit a gas boiler in an existing home in England, Approved Document L Volume 1 expects at least 92% efficiency (ErP), thermostatic control in each heated room, a boiler interlock, and, for a combi, one extra energy saving measure such as weather compensation or a smart thermostat with automation and optimisation. New or fully replaced wet systems should be sized to heat the home at a flow temperature of no more than 55°C. These rules are the same in the 2021 edition in force now and the 2026 edition that takes effect on 24 March 2027; where the new edition adds something, we say so. This guide sets out the rules that come up on the job and in the BPEC Part L exam.

Minimum boiler efficiencies

These minimums apply in existing dwellings. Best practice is to beat them. Exceptional circumstances are defined in the government's Guide to the Condensing Boiler Installation Assessment Procedure for Dwellings.

SystemMinimum efficiencyExceptional circumstances
Gas wet heating (boiler with radiators or UFH)92% (ErP)78% natural gas, 80% LPG (SEDBUK 2009)
Gas range cooker with integral boiler75% (SEDBUK 2009)None given
Oil regular boiler91% (ErP)84% (SEDBUK 2009)
Oil combi boiler86% (SEDBUK 2009)82%

The extra measure for a gas combi

Fitting a gas combination boiler in an existing home means also fitting at least one of these, as suits the system:

  • Flue gas heat recovery
  • Weather compensation
  • Load compensation
  • A smart thermostat with automation and optimisation

Sizing and the 55°C flow temperature

Where a wet heating system is newly installed or fully replaced (boiler, emitters and pipework), every part should be sized so the system meets the home's heating needs at a maximum flow temperature of 55°C. In an existing home where that isn't feasible, for example there's no room for bigger radiators, design to the lowest flow temperature that still heats the home. The 2026 edition adds a note that the 55°C rule covers space heating only, not hot water.

Size the system from a proper heat loss calculation and don't oversize it. A gas combi should be chosen so it can modulate down to the typical heating load of the home. The 2026 edition spells this out further: a room-by-room heat loss calculation for a new system, a whole-dwelling calculation when only the boiler is replaced, sizing from the old boiler's output is not acceptable, and the combi should modulate to the typical mid-season load.

Controls you must fit

In a new home, or when a boiler or other heat generator is replaced, each heated room needs thermostatic control. That can be a room thermostat with TRVs on every radiator outside that room (but not in the room with the thermostat; the 2026 edition adds that radiators there have manual valves), a thermostat in each room or zone, or networked controls on each emitter. A zone can replace individual rooms in a single-storey open-plan home where the living area is over 70% of the floor area, or for two similar adjoining rooms such as a kitchen and utility.

  • Wire the system so the boiler and pump switch off when there is no demand for heating or hot water. The 2026 edition also allows them to drop to a reduced output temperature instead.
  • Fit a boiler interlock whenever you work on a system with a boiler.
  • Hot water from a store needs its own time control and electronic temperature control. A replacement cylinder needs electronic temperature control such as a cylinder thermostat.
  • Existing heating and hot water on one time controller may stay that way; otherwise they need separate time controls.
  • New homes of 150 m² or more need at least two independently controlled heating circuits.
  • Use fully pumped primary circulation where the heat source allows it, and make sure there is a minimum flow to stop short-cycling.

Official sources

Practise for it

Test yourself with a free timed mock, with every answer explained.

Start a free mock

Frequently asked questions

What is the minimum boiler efficiency under Part L?

92% (ErP) for a gas boiler on a wet system in an existing home, and 91% for an oil regular boiler. Lower figures are only allowed in exceptional circumstances defined by the condensing boiler assessment procedure.

Do I have to fit weather compensation with a new combi?

Not necessarily. Part L asks for at least one of flue gas heat recovery, weather compensation, load compensation, or a smart thermostat with automation and optimisation when a gas combi goes into an existing home.

Does every new heating system have to run at 55°C?

A new or fully replaced wet system should be sized to meet the heating need at a maximum flow temperature of 55°C. In an existing home where that isn't feasible, design for the lowest flow temperature that works. Boiler-only swaps don't trigger the 55°C rule, but the 2026 edition asks for a whole-dwelling heat loss calculation to size the new boiler.

Can I put a TRV in the same room as the room thermostat?

No. Approved Document L says TRVs shouldn't be used in the same room as the thermostat. Radiators in that room should have manual controls.

Do I need a qualification to do this work?

Replacing a boiler is notifiable work. Most installers self-certify through a competent person scheme, and the BPEC Part L energy efficiency course is a common way to show the scheme you know the rules.