Extract fan rates: the Part F minimums for kitchens, bathrooms and WCs
Updated 2 November 2026. Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).
Approved Document F sets the minimum extract rate for each wet room in a dwelling. For an intermittent fan that is 30 l/s for a kitchen with a cooker hood that vents outside (60 l/s without one), 30 l/s for a utility room, 15 l/s for a bathroom and 6 l/s for a WC. Continuous systems use lower high rates instead: 13 l/s kitchen, 8 l/s utility and bathroom, 6 l/s WC. These figures are the same in the 2021 edition in force now and the 2026 edition that takes effect on 24 March 2027. This guide puts the tables in one place with the rules for fan position, whole dwelling ventilation and commissioning.
Which rooms need extract ventilation?
Paragraph 1.13 says extract ventilation to the outside should be provided in every kitchen, utility room, bathroom and sanitary accommodation (WC). It can be intermittent (a fan that runs when needed) or continuous (a fan that runs all the time with a boost setting).
Fans and extract terminals, other than cooker hoods, should be fitted as high as practicable and no more than 400 mm below the ceiling. A cooker hood that extracts outside goes at the height in the manufacturer's instructions, or 650 mm to 750 mm above the hob if there is none. A recirculating cooker hood on its own does not count as ventilation for Part F.
Intermittent extract rates (Table 1.1)
These are the minimum rates for a fan that runs intermittently. The kitchen figure depends on whether the cooker hood extracts to the outside.
| Room | Minimum intermittent rate |
|---|---|
| Kitchen, cooker hood extracting outside | 30 l/s |
| Kitchen, no cooker hood or hood does not extract outside | 60 l/s |
| Utility room | 30 l/s |
| Bathroom | 15 l/s |
| Sanitary accommodation (WC) | 6 l/s (or use the purge ventilation guidance instead) |
Continuous extract rates (Table 1.2)
A continuous extract system has a high (boost) rate for each room and a continuous rate for normal running. Add up the continuous rates of all the extract points in the dwelling: the total should be at least the whole dwelling ventilation rate. If a room's continuous rate already meets its minimum high rate, nothing extra is needed there.
| Room | Minimum high rate |
|---|---|
| Kitchen | 13 l/s |
| Utility room | 8 l/s |
| Bathroom | 8 l/s |
| Sanitary accommodation (WC) | 6 l/s |
Whole dwelling ventilation rate (Table 1.3)
Supply air to the habitable rooms comes through background ventilators or continuous supply fans. The minimum rate is the higher of two figures: 0.3 l/s for every m² of internal floor area (all floors added together), and the rate for the number of bedrooms below. A dwelling with only one habitable room uses 13 l/s. For more than five bedrooms, add 6 l/s for each extra bedroom.
Example: a three-bedroom house with 110 m² of floor area. 110 × 0.3 = 33 l/s, which beats the 31 l/s bedroom figure, so the design rate is 33 l/s.
| Bedrooms | Minimum rate |
|---|---|
| 1 | 19 l/s |
| 2 | 25 l/s |
| 3 | 31 l/s |
| 4 | 37 l/s |
| 5 | 43 l/s |
Background ventilators and door undercuts
For natural ventilation, Table 1.7 gives background ventilator sizes as equivalent area: 8000 mm² for each habitable room and kitchen in a dwelling with more than one floor, 10,000 mm² in a single-storey dwelling, and 4000 mm² for a bathroom. A dwelling needs at least five ventilators in its habitable rooms and kitchen (four in a one-bedroom home), and an open-plan kitchen and living room needs at least three.
Air has to move between rooms, so internal doors need a free area equal to a 10 mm undercut on a 760 mm door: 10 mm above the floor finish, or 20 mm above the floor surface if the finish isn't down yet.
Adding a fan or a wet room to an existing home
When a wet room is added to an existing dwelling, paragraph 3.25 allows an intermittent fan at the Table 1.1 rate with a background ventilator of at least 5000 mm², a continuous fan at the Table 1.2 rate, or a single-room heat recovery unit. A single-room heat recovery unit runs at the Table 1.2 high rate with half of that as its continuous rate, and doesn't need a background ventilator in the same room.
Testing and commissioning
Every mechanical fan in a new dwelling should have its air flow measured, including intermittent fans and cooker hoods. Use a calibrated air flow device with a proprietary hood, accurate to ±5% and calibrated in the last 12 months at a UKAS-accredited centre. Background ventilators should be open and doors and windows shut, and each reading goes on the commissioning sheet in l/s. The results go to building control no later than five days after the final test.
The 2026 edition, from 24 March 2027, adds more detail: a powered flow hood for continuous fans (a vane anemometer is still allowed for intermittent fans), readings averaged over at least 10 seconds, and testing in existing homes for new centralised systems, new fans on more than 2 m of duct, and new fans on duct with more than one 90 degree offset. It also says a single intermittent fan in an existing home needs someone with appropriate training, while other mechanical ventilation should be commissioned by a member of a scheme that checks competence.
Official sources
Practise for it
Test yourself with a free timed mock, with every answer explained.
Start a free mockFrequently asked questions
What extract rate does a bathroom fan need?
At least 15 l/s for an intermittent fan, or a high rate of at least 8 l/s for a continuous fan, under Approved Document F Tables 1.1 and 1.2.
What extract rate does a kitchen need?
30 l/s if a cooker hood extracts to the outside, or 60 l/s for a fan elsewhere in the room if there is no hood or the hood recirculates. A continuous system needs a 13 l/s high rate.
What size fan does a toilet need?
6 l/s, whether intermittent or continuous. Part F also allows purge ventilation, such as an opening window of the right size, as an alternative for a WC.
How high should an extract fan be?
As high as practicable in the room and no more than 400 mm below the ceiling. Cooker hoods follow the manufacturer's height, or 650 mm to 750 mm above the hob.
Does a new extract fan need testing?
In a new dwelling, yes: every fan's air flow is measured and the results sent to building control within five days. From 24 March 2027, the 2026 edition also asks for testing in existing homes where a new fan is on more than 2 m of duct or more than one 90 degree offset, or is part of a new centralised system.
Related
Sources: Approved Document F Volume 1: Dwellings, 2021 edition and 2026 edition (gov.uk). This guide paraphrases the rules for revision; always work from the current official documents.