Domestic Ventilation: Ventilation rates and system types practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

33 of our 90 Domestic Ventilation Systems (DOM-VENT) questions are on ventilation rates and system types, about 37% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. What is the minimum high rate for a kitchen served by a continuous mechanical extract system?

Show answer

Answer: D. 13 l/s

  • Table 1.2 sets the kitchen high rate for continuous extract at 13 l/s.
  • If the continuous rate already meets the high rate, no extra ventilation is needed.

Continuous systems run all day, so their boost rates are lower than intermittent fans.

Why the others are wrong:

A: 30 l/s is an intermittent rate, for a kitchen with a ducted hood.

B: 8 l/s is the continuous high rate for a bathroom or utility room.

C: 60 l/s is the intermittent kitchen rate without a ducted hood.

Memory trick:

Continuous kitchen: lucky 13.

Find it in the book

Approved Document F Vol 1 2021, page 10; 2026 edition, page 9

Reg Approved Document F Vol 1, 2021 and 2026 editions, Table 1.2

Q2. Based on the number of bedrooms alone, what is the minimum whole dwelling ventilation rate for a seven-bedroom house?

Show answer

Answer: C. 55 l/s

  • Table 1.3 stops at five bedrooms with 43 l/s.
  • Note 2 adds 6 l/s for each extra bedroom: 43 + 6 + 6 = 55 l/s.

The floor area rate of 0.3 l/s per m² must still be checked and the higher figure used.

Why the others are wrong:

A: 43 l/s is the five-bedroom value; two more bedrooms must be added.

B: 49 l/s is the six-bedroom value; one bedroom short.

D: 61 l/s would be an eight-bedroom house.

The maths

Five bedrooms = 43 l/s
Extra bedrooms = 7 - 5 = 2
43 + (2 x 6) = 55 l/s

Memory trick:

Past five, add six a bed.

Find it in the book

Approved Document F Vol 1 2021, page 10; 2026 edition, page 9

Reg Approved Document F Vol 1, 2021 and 2026 editions, Table 1.3 Note 2

Q3. A naturally ventilated house has a kitchen with a recirculating cooker hood, a utility room, a family bathroom, an en suite and a separate WC, each with its own intermittent fan. What is the combined minimum extract rate of all the fans?

Show answer

Answer: D. 126 l/s

  • Table 1.1: kitchen without a ducted hood 60, utility 30, bathroom 15, en suite 15, WC 6 l/s.
  • Total: 126 l/s.

An en suite contains a bath or shower, so it takes the bathroom rate.

Why the others are wrong:

A: this uses 30 l/s for the kitchen, which only applies when the hood extracts outside.

B: this misses the en suite, which counts as a bathroom at 15 l/s.

C: this leaves out the 6 l/s WC fan.

The maths

Kitchen (recirculating hood) = 60 l/s
Utility 30 + bathroom 15 + en suite 15 + WC 6 = 66 l/s
60 + 66 = 126 l/s

Memory trick:

Recirc kitchen 60, add the rest room by room.

Find it in the book

Approved Document F Vol 1 2021, page 8; 2026 edition, page 7

Reg Approved Document F Vol 1, 2021 and 2026 editions, Table 1.1

Q4. A new flat is formed entirely in a basement. Which ventilation approach does AD F say is not appropriate?

Show answer

Answer: A. Natural ventilation using background vents and intermittent fans

  • A basement-only dwelling is treated as a single-storey dwelling above ground.
  • The natural ventilation guidance is not appropriate for it.

Below ground, natural ventilation cannot be relied on in the same way.

Why the others are wrong:

B: continuous MEV is not ruled out for a basement-only dwelling.

C: MVHR is not ruled out for a basement-only dwelling.

D: AD F says to follow that guidance, treating the flat as single-storey.

Memory trick:

All below ground? No natural route.

Find it in the book

Approved Document F Vol 1 2021, page 13; 2026 edition, page 12

Reg Approved Document F Vol 1, 2021 para 1.41; 2026 edition para 1.37

Q5. What is the minimum total continuous rate for an MVHR system in a dwelling?

Show answer

Answer: D. The whole dwelling ventilation rate

  • MVHR must deliver at least the whole dwelling ventilation rate continuously.
  • Each wet room must also reach its Table 1.2 high rate.

Supply is shared between habitable rooms in proportion to their volume.

Why the others are wrong:

A: the high rates set the boost in each wet room, not the total continuous rate.

B: four air changes per hour is the purge ventilation standard.

C: 13 l/s is the figure for a dwelling with only one habitable room.

Memory trick:

MVHR baseline = whole house rate.

Find it in the book

Approved Document F Vol 1 2021, pages 10 and 16; 2026 edition, pages 9 and 16

Reg Approved Document F Vol 1, 2021 para 1.69, Table 1.3; 2026 edition paras 1.69, 1.20

Q6. According to Table 1.6, which dwellings is the natural ventilation guidance (background ventilators plus intermittent extract fans) suitable for?

Show answer

Answer: A. Less airtight dwellings only

  • Natural ventilation guidance covers less airtight dwellings only.
  • Continuous MEV and MVHR cover all dwellings, including highly airtight ones.

A very tight home relies less on infiltration, so it needs fan-driven whole dwelling ventilation.

Why the others are wrong:

B: the natural ventilation route is excluded for highly airtight dwellings.

C: only continuous MEV and MVHR cover both less airtight and highly airtight dwellings.

D: basements have their own guidance; Table 1.6 links natural ventilation to airtightness, not basements.

Memory trick:

Tight house? Fans, not just trickles.

Find it in the book

Approved Document F Vol 1 2021, page 14; 2026 edition, page 14

Reg Approved Document F Vol 1, 2021 and 2026 editions, Table 1.6

Want 84 more Domestic Ventilation questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other Domestic Ventilation topics

Free official guides for this topic

Our questions are written from these documents. Download them free to revise from the source.

© Crown copyright (GOV.UK). Unchanged copies, reproduced under the Open Government Licence v3.0. FreeMocks is not connected to or endorsed by HSE or the government.

Revise this topic