Q1. A single-storey bungalow is naturally ventilated. What minimum equivalent area of background ventilator does the kitchen need?
Show answer
Answer: C. 10,000mm²
- In a single-storey dwelling, kitchens and habitable rooms each need 10,000mm².
- Utility rooms and sanitary accommodation have no minimum.
Always check which column of Table 1.7 applies: multiple floors or single storey.
Why the others are wrong:
A: 8000mm² is the kitchen figure for a dwelling with multiple floors.
B: 4000mm² is the bathroom figure.
D: there is no minimum for utility rooms and WCs, but kitchens do have one.
Memory trick:
Bungalow? Go to ten.
Find it in the book
Approved Document F Vol 1 2021, page 15; 2026 edition, page 15