Domestic Ventilation: Background, purge and existing dwellings practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

30 of our 90 Domestic Ventilation Systems (DOM-VENT) questions are on background, purge and existing dwellings, about 33% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A single-storey bungalow is naturally ventilated. What minimum equivalent area of background ventilator does the kitchen need?

Show answer

Answer: C. 10,000mm²

  • In a single-storey dwelling, kitchens and habitable rooms each need 10,000mm².
  • Utility rooms and sanitary accommodation have no minimum.

Always check which column of Table 1.7 applies: multiple floors or single storey.

Why the others are wrong:

A: 8000mm² is the kitchen figure for a dwelling with multiple floors.

B: 4000mm² is the bathroom figure.

D: there is no minimum for utility rooms and WCs, but kitchens do have one.

Memory trick:

Bungalow? Go to ten.

Find it in the book

Approved Document F Vol 1 2021, page 15; 2026 edition, page 15

Reg Approved Document F Vol 1, 2021 and 2026 editions, Table 1.7

Q2. A new en suite is added to an existing house using intermittent extract. What background ventilator should be provided in the room?

Show answer

Answer: B. At least 5000mm² equivalent area

  • Adding a wet room with intermittent extract needs the Table 1.1 rate and a background ventilator of at least 5000mm².
  • Alternatives: continuous extract (Table 1.2) or a single-room heat recovery ventilator.

Whole dwelling ventilation should also be extended to the new room.

Why the others are wrong:

A: 4000mm² is the bathroom figure in Table 1.7 for a new natural ventilation design.

C: 8000mm² is the habitable room figure for multi-storey natural ventilation.

D: 2500mm² is below the figure for adding a wet room.

Memory trick:

New wet room: fan plus 5000.

Find it in the book

Approved Document F Vol 1 2021, page 26; 2026 edition, page 26

Reg Approved Document F Vol 1, 2021 and 2026 editions, para 3.25

Q3. A naturally ventilated flat has a façade facing a busy main road with constant traffic noise. What background ventilator should be fitted there?

Show answer

Answer: D. A noise attenuating background ventilator

  • Where an exposed façade is near sustained, loud noise, fit a noise attenuating background ventilator.
  • Background ventilators are intended to be left open.

Outside noise also affects whether windows suit purge ventilation.

Why the others are wrong:

A: the room still needs background ventilation; the vent type changes.

B: vents are meant to stay open; a noise attenuating type is needed.

C: a night latch is not adequate background ventilation.

Memory trick:

Noisy road? Acoustic trickle vent.

Find it in the book

Approved Document F Vol 1 2021, page 15; 2026 edition, page 15

Reg Approved Document F Vol 1, 2021 and 2026 editions, para 1.54

Q4. A new flat faces a busy urban road. Where should the ventilation air intakes ideally be located?

Show answer

Answer: C. As high as possible and on the less polluted side of the building

  • Next to busy urban roads, intakes should be as high as possible.
  • They should sit on the less polluted side of the building.

Mechanical ventilation is often the most practical way to achieve this.

Why the others are wrong:

A: intakes next to busy roads should be high and on the less polluted side.

B: enclosed courtyards where pollutants are discharged should be avoided for intakes.

D: intakes and outlets should be separated so exhaust air is not drawn back in.

Memory trick:

Road outside? Breathe high, breathe round the back.

Find it in the book

Approved Document F Vol 1 2021, page 20; 2026 edition, page 20

Reg Approved Document F Vol 1, 2021 and 2026 editions, para 2.3

Q5. A new conservatory is added to a house. Above what floor area do the Part F requirements apply?

Show answer

Answer: B. 30 m²

  • Conservatories with a floor area not exceeding 30 m² are exempt from Part F.
  • Larger ones follow paragraphs 3.22 to 3.24, including the through-room guidance.

The through-room guidance applies whatever ventilation the adjoining room already has.

Why the others are wrong:

A: 25 m² is not the threshold.

C: 40 m² is not the threshold; it is lower than this.

D: 50 m² is not the threshold; it is lower than this.

Memory trick:

Conservatory over 30? Part F kicks in.

Find it in the book

Approved Document F Vol 1 2021, page 26; 2026 edition, page 26

Reg Approved Document F Vol 1, 2021 and 2026 editions, para 3.21

Q6. A four-bedroom house is fitted with continuous MEV. Which background ventilator provision meets AD F?

Show answer

Answer: B. Six, none in wet rooms, each habitable room at least 4000mm²

  • With continuous MEV, the number of ventilators is bedrooms + 2: 4 + 2 = 6.
  • Each habitable room needs at least 4000mm², and none go in wet rooms.

The fan pulls air out of the wet rooms, so fresh air should enter through the habitable rooms.

Why the others are wrong:

A: with MEV, background ventilators must not be in wet rooms, and four bedrooms plus two gives six.

C: 8000mm² is the natural ventilation figure; with MEV the minimum is 4000mm² per habitable room.

D: the count is bedrooms plus two, so four is too few.

The maths

Bedrooms = 4
Ventilators = 4 + 2 = 6
Each habitable room: at least 4000mm²

Memory trick:

MEV vents: beds plus two, never in the wet.

Find it in the book

Approved Document F Vol 1 2021, page 16; 2026 edition, page 16

Reg Approved Document F Vol 1, 2021 and 2026 editions, para 1.64

Want 84 more Domestic Ventilation questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other Domestic Ventilation topics

Free official guides for this topic

Our questions are written from these documents. Download them free to revise from the source.

© Crown copyright (GOV.UK). Unchanged copies, reproduced under the Open Government Licence v3.0. FreeMocks is not connected to or endorsed by HSE or the government.

Revise this topic