2391-50: Testing practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

162 of our 320 Initial Verification (2391-50) questions are on testing, about 51% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our testing questions test most often. Know where these are in your book before the exam.

  • 643.2 · 32 questions
  • 643.7 · 22 questions
  • 643.3 · 17 questions
  • 643.6 · 5 questions
  • 411.5 · 3 questions
  • 643.1 · 3 questions
  • 418.3 · 2 questions
  • 643.5 · 2 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A new lighting circuit is protected by a 6 A Type B circuit-breaker. Ze is 0.35 Ω and (R1 + R2) measured during continuity testing is 1.40 Ω. What is Zs and does it satisfy the 0.8 rule of thumb against the Table 41.3 value of 7.28 Ω?

Show answer

Answer: B. 1.75 Ω, which is well within the 5.82 Ω limit

  • Zs = Ze + (R1 + R2) = 0.35 + 1.40 = 1.75 Ω.
  • Rule-of-thumb limit = 7.28 x 0.8 = 5.82 Ω.
  • 1.75 Ω is comfortably below 5.82 Ω.

GN3 prefers this Ze plus (R1 + R2) method for final circuits.

Why the others are wrong:

A: this subtracts Ze from (R1 + R2) instead of adding them.

C: 1.46 Ω is not 0.8 x 7.28; the limit is 5.82 Ω.

D: this multiplies Ze by (R1 + R2); the values must be added.

The maths

Zs = Ze + (R1 + R2) = 0.35 + 1.40 = 1.75 Ω
Limit = 0.8 x 7.28 = 5.82 Ω
1.75 < 5.82, acceptable

Memory trick:

Zs: external plus circuit, then check against 80 % of the table.

Reg GN3 2.6.15; Table 41.3

Q2. A new cooker circuit is 24 m of 6 mm²/2.5 mm² twin and earth (10.49 mΩ/m at 20 °C) on a 40 A Type B circuit-breaker. Ze is 0.35 Ω. Using GN3's multiplier of 1.20 to bring (R1 + R2) to 70 °C, what is the corrected Zs and does it meet Table 41.3?

Show answer

Answer: D. 0.65 Ω, within the 1.09 Ω limit

  • (R1 + R2) at 20 °C = 24 x 10.49 / 1000 = 0.25 Ω
  • At 70 °C: 0.25 x 1.20 = 0.30 Ω
  • Zs = 0.35 + 0.30 = 0.65 Ω, below 1.09 Ω (40 A Type B)

Only the circuit conductors warm up, so the 1.20 multiplier is applied to (R1 + R2), not to Ze.

Why the others are wrong:

A: 0.55 Ω is the Table 41.3 value for a 40 A Type C device, not Type B.

B: that is the uncorrected Zs; the 1.20 multiplier has not been applied to (R1 + R2).

C: 19.51 mΩ/m is for 2.5/1.5 mm² cable, not 6/2.5 mm².

The maths

Step 1: 24 x 10.49 = 251.8 mΩ = 0.252 Ω
Step 2: 0.252 x 1.20 = 0.302 Ω
Step 3: Zs = 0.35 + 0.302 = 0.652 Ω
0.65 Ω < 1.09 Ω, so it complies

Memory trick:

Heat the cable (x 1.20), not the supply.

Find it in the book

BS 7671:2018+A4:2026, page 75; IET Guidance Note 3 (2022 edition), page 178

Reg Table 41.3; GN3 Appendix A3, Table B1

Q3. A new 2.4 m earth rod is being tested by fall of potential. An apprentice has placed the current spike 15 m from the rod. What is wrong?

Show answer

Answer: C. It is too close: the current spike should be at least 24 m away

  • GN3: current spike at least 10 x the maximum dimension of the electrode system
  • 10 x 2.4 m = 24 m
  • At 15 m the resistance areas may overlap, giving unreliable readings

The voltage spike is then placed midway and 10 % either side.

Why the others are wrong:

A: the spike needs distance, otherwise the resistance areas overlap.

B: GN3 asks for at least ten times the maximum dimension of the electrode system.

D: twenty times is more than needed; ten times the 2.4 m rod is 24 m.

The maths

Minimum distance = 10 x 2.4 m = 24 m
15 m < 24 m, so the spike must be moved further out

Memory trick:

Rod length times ten for the current spike.

Find it in the book

IET Guidance Note 3 (2022 edition), page 80

Reg 643.7.2; GN3 2.6.13

Q4. You check a new three-phase supply to a motor with an indicator lamp type phase sequence tester. The L1/L3/L2 lamp lights rather than the L1/L2/L3 lamp. What does this tell you?

Show answer

Answer: A. The sequence is reversed and the motor would run anticlockwise

  • Lamp type indicators light either the L1/L2/L3 lamp (correct, clockwise) or the L1/L3/L2 lamp (reversed, anticlockwise).
  • Swapping any two lines reverses the sequence.
  • GN3 recommends checking rotation at the point closest to the load, before it is energized.

A reversed indication means two lines need swapping before the motor is run.

Why the others are wrong:

B: the lamp tester shows the order of the three lines; an L1/L3/L2 indication means reversed sequence, not loss of a phase.

C: correct L1-L2-L3 sequence lights the L1/L2/L3 lamp, not the L1/L3/L2 lamp.

D: the tester compares the three lines; a neutral fault is found by polarity testing.

Memory trick:

1-2-3 is clockwise; 1-3-2 means swap two.

Find it in the book

IET Guidance Note 3 (2022 edition), page 94

Reg 643.9; GN3 2.6.17

Q5. Steel conduit is used as the circuit protective conductor. What does GN3 say is needed to verify it?

Show answer

Answer: D. Inspect along its length, then do a standard continuity test

  • Where conduit, trunking or SWA is the cpc: inspect the enclosure along its length for soundness of construction.
  • Then perform the standard continuity test.

Both are needed; a reading alone can hide a poor joint about to fail.

Why the others are wrong:

A: GN3 requires the enclosure to be inspected for soundness as well.

B: the standard continuity test methods apply to metallic enclosures too.

C: insulation testing does not prove continuity of a protective conductor.

Memory trick:

Metal cpc: look along it, then test it.

Reg 643.2.1

Q6. In a wet area (not a bath, shower or pool location), up to what voltage is basic protection by insulation generally not needed for SELV?

Show answer

Answer: D. 12 V AC or 30 V DC

  • Basic protection by insulation is generally not required for SELV/PELV up to 12 V AC or 30 V DC in wet areas, and 25 V AC or 60 V DC in dry areas.
  • In bath/shower rooms, pools and saunas it is required at all voltages.

GN3 says it is often easier to insulation test these circuits anyway.

Why the others are wrong:

A: those are the limits for dry areas.

B: those are the ELV limits, not the insulation thresholds.

C: GN3 gives 12 V AC or 30 V DC for wet areas.

Memory trick:

Wet 12/30, dry 25/60.

Reg 414.4.5

Want 314 more 2391-50 questions? Start a free timed mock.