2391-50: Safety and test instruments practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

26 of our 320 Initial Verification (2391-50) questions are on safety and test instruments, about 8% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. You need fused test leads for earth fault loop impedance tests. What fuse rating does GN3 say is typically needed?

Show answer

Answer: D. 7 A or 10 A

  • Fused leads add resistance; a 500 mA fuse can add up to 1.8 ohm in a lead pair.
  • For loop testing, leads need higher rated fuses, typically 7 A or 10 A, to stop the test current rupturing the fuse.
  • Leads to HSE GS38 should be adequate.

Why the others are wrong:

A: a 500 mA fuse can add up to 1.8 ohm and may rupture under the test current.

B: 2 A is still too low for the test currents of a loop tester.

C: this is far higher than GN3 suggests for test leads.

Memory trick:

Loop leads: 7 or 10, not half an amp.

Reg GN3 4.5

Q2. During a continuity test, the digital reading on your low-resistance ohmmeter keeps changing and will not settle. What does GN3 suggest is the likely cause?

Show answer

Answer: C. Interference pick-up from an external AC source

  • Field errors in low-resistance tests include contact resistance, lead resistance, AC interference and thermocouple effects.
  • Interference pick-up from an external AC source cannot be eliminated; it may show as an unstable digital readout or a vibrating analogue pointer.

Lead resistance can be nulled, and thermocouple effects removed by reversing the probes and averaging.

Why the others are wrong:

A: thermocouple effects are cancelled by reversing and averaging, not shown by an unstable display.

B: charging is an issue with insulation resistance tests at high voltage.

D: un-nulled leads give a steady but high reading, not an unstable one.

Memory trick:

Jumpy display = AC noise getting in.

Reg GN3 4.3

Q3. An industrial installation has a 3 A time-delayed RCD on a sub-main. What does GN3 say about typical RCD testers?

Show answer

Answer: B. Their range is generally limited to 10 mA to 1 A

  • RCD testers should apply the full range of test current within the accuracy of BS EN 61557-6.
  • The range of RCD operating currents supported is generally 10 mA to 1 A.
  • Going beyond these limits has severe design and cost implications.

A 3 A device would need specialist equipment or an alternative method.

Why the others are wrong:

A: GN3 says exceeding about 1 A has severe design and cost implications.

C: they typically cover from 10 mA up to 1 A.

D: fused leads do not extend an instrument's test current range.

Memory trick:

RCD testers: 10 mA up to 1 A.

Reg GN3 4.7

Q4. Your insulation and continuity tester falls from a stepladder onto a concrete floor but still powers up. What should you do before continuing?

Show answer

Answer: B. Check it for damage and confirm safety and accuracy

  • GN3: it is essential that an instrument is inspected for damage and its safety and accuracy confirmed after any mechanical or electrical mishandling.
  • A check box or comparison with another instrument can be used for an intermediate check.

Damaged instruments can give wrong results or create a hazard.

Why the others are wrong:

A: an instrument that turns on may still be unsafe or inaccurate.

C: an unknown error cannot be corrected with a fixed allowance.

D: GN3 says checks are essential after any mishandling, not at the next due date.

Memory trick:

Dropped it? Check it before you trust it.

Reg GN3 4.2

Q5. A manufacturer says its tester has robust internal electrical protection, so non-fused leads may be used. What caution does GN3 add?

Show answer

Answer: B. Its protection does not extend to the leads and probes

  • Some manufacturers advise non-fused leads where the instrument has robust internal protection.
  • GN3 warns that such protection does not extend to the probes and leads.
  • Where unsure, carry out a risk assessment on whether fused leads are needed.

The leads are where faults at the probe tip occur.

Why the others are wrong:

A: GN3 notes some manufacturers advise non-fused leads where the instrument is protected.

C: the category rating does not change the lead protection issue.

D: GN3 suggests a risk assessment where unsure, not a blanket rule.

Memory trick:

The box is protected, the wires are not.

Reg GN3 4.1

Q6. You are considering an extra live test at a board during initial verification, though it will not add useful information. What is HSE advice as quoted in GN3?

Show answer

Answer: C. Only carry out live tests that are useful and informative

  • The HSE advises carrying out only live tests that are actually useful and informative, to minimise danger.
  • The inspector should always consider whether a live test is necessary before doing it.
  • GS38 measures apply to all instruments, leads, probes and accessories.

Why the others are wrong:

A: unnecessary live tests add risk without benefit.

B: PPE does not justify a test that is not needed.

D: some live tests, such as Zs and RCD tests, are required.

Memory trick:

No point, no live test.

Reg GN3 4.1