2391-50: Initial inspection practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

64 of our 320 Initial Verification (2391-50) questions are on initial inspection, about 20% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our initial inspection questions test most often. Know where these are in your book before the exam.

  • 421.1 · 5 questions
  • 522.6 · 5 questions
  • 559.5 · 4 questions
  • 544.1 · 3 questions
  • 701.32 · 3 questions
  • 416.2 · 2 questions
  • 514.10 · 2 questions
  • 514.4 · 2 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. For temporary overvoltages caused by LV system faults such as loss of neutral, what does GN3 say the inspector should normally check on a new 230/400 V installation?

Show answer

Answer: A. Cables and equipment have suitable voltage ratings

  • There is usually little the designer can do beyond selecting equipment with suitable insulation voltage ratings.
  • For example, 600/1000 V cables on a 230/400 V installation.
  • The inspector should check this has been done.

Why the others are wrong:

B: SPDs address transient overvoltages, not these temporary overvoltages.

C: that relates to HV system faults with private substations.

D: GN3 does not require this.

Memory trick:

Loss of neutral? Check the cable voltage rating.

Reg GN3 2.6.21

Q2. On a TT installation, the earthing conductor from the MET to the earth rod is bare copper buried directly in the ground, with no protection against corrosion. What minimum csa should the inspector expect?

Show answer

Answer: C. 25 mm² copper

Table 54.1, buried earthing conductors:

  • protected against corrosion and mechanical damage: 2.5 mm² copper;
  • protected against corrosion but not mechanical damage: 16 mm² copper;
  • not protected against corrosion: 25 mm² copper (50 mm² steel).

A bare buried conductor needs 25 mm² copper.

Why the others are wrong:

A: 16 mm² copper applies where the conductor is protected against corrosion but not against mechanical damage.

B: 10 mm² is not a Table 54.1 copper figure; unprotected against corrosion needs 25 mm².

D: 2.5 mm² applies only where protected against both corrosion and mechanical damage.

Memory trick:

Bare in the dirt = 25: the soil eats the rest.

Reg 542.3.1, Table 54.1

Q3. A new consumer unit from one maker has been fitted with two RCBOs of a different make. The consumer unit maker's literature does not list them as suitable. What should the inspector conclude?

Show answer

Answer: A. Not compliant; only devices the board maker approves

  • 536.4.203: in BS EN 61439 assemblies (consumer units, distribution boards), incorporated devices and components shall only be those declared suitable according to the assembly manufacturer's instructions or literature.
  • The A4 checklist item 7.8 asks the inspector to confirm this.

Mixing brands without the maker's approval breaks the assembly's verified design.

Why the others are wrong:

B: product standard compliance alone does not make them suitable for that assembly.

C: physical fit does not prove suitability.

D: correct torque does not overcome the assembly requirement.

Memory trick:

Mix and match? Only if the board maker says so.

Find it in the book

BS 7671:2018+A4:2026, page 192

Reg 536.4.203

Q4. On a new house, the Appendix 6 inspection checklist includes 30 mA RCD additional protection for lighting. Which circuits does this item cover?

Show answer

Answer: A. Final circuits supplying luminaires in dwellings

  • The checklist lists RCD additional protection for final circuits supplying luminaires within domestic (household) premises (411.3.4).
  • Other items cover socket-outlets up to 32 A, outdoor mobile equipment and concealed cables.

In a new house, every lighting circuit needs 30 mA RCD protection.

Why the others are wrong:

B: the requirement covers all domestic luminaire circuits, not just bathrooms.

C: indoor domestic lighting circuits are included too.

D: the fitting material does not decide it.

Memory trick:

Domestic lights: all on 30 mA.

Reg 411.3.4; Appendix 6 (checklist 8.18)

Q5. A non-flame-propagating PVC trunking with internal dimensions of 38 mm x 25 mm passes through a fire-rated wall. Both the trunking and its terminations satisfy IP33. Does it need to be internally sealed?

Show answer

Answer: D. Yes, its internal area of 950 mm² exceeds 710 mm²

  • 527.2.2: containment through a fire-rated element must be sealed internally as well as externally.
  • 527.2.3 exemption: non-flame-propagating systems with a maximum internal csa of 710 mm² need not be internally sealed if the system and terminations satisfy IP33.
  • 38 x 25 = 950 mm², so the exemption does not apply.

All three conditions must be met for the exemption.

Why the others are wrong:

A: systems up to 710 mm² meeting the IP33 conditions need not be.

B: that classification alone does not remove the need for internal sealing above 710 mm².

C: IP33 only helps where the internal area is 710 mm² or less.

The maths

Internal csa = 38 mm x 25 mm = 950 mm².
950 mm² > 710 mm², so the 527.2.3 exemption cannot apply even though IP33 is met.
Result: internal fire sealing required (527.2.2).

Memory trick:

710 mm²: about a 30 mm hole. Bigger than that, seal inside.

Find it in the book

BS 7671:2018+A4:2026, page 159

Reg 527.2.3

Q6. Which emergency switching arrangement for a workshop machine meets BS 7671?

Show answer

Answer: C. Red button on yellow, readily accessible, opening the main circuit

  • 537.3.3.3: plugs and socket-outlets shall not be provided for emergency switching off.
  • 537.3.3.4: remote control switching shall be opened by de-energization of coils or other failure-to-safety means.
  • 537.3.3.5: operating means identified preferably by colour: RED on a contrasting background (for example yellow).
  • 537.3.3.6: readily accessible where danger might occur.

Why the others are wrong:

A: remote operation must work by de-energizing coils, a fail-safe method.

B: plugs and socket-outlets shall not be used for emergency switching off.

D: if colour is used it shall be red on a contrasting background.

Memory trick:

Emergency stop: red on yellow, fails safe, never a plug.

Find it in the book

BS 7671:2018+A4:2026, page 196

Reg 537.3.3

Want 314 more 2391-50 questions? Start a free timed mock.