Q1. For temporary overvoltages caused by LV system faults such as loss of neutral, what does GN3 say the inspector should normally check on a new 230/400 V installation?
Show answer
Answer: A. Cables and equipment have suitable voltage ratings
- There is usually little the designer can do beyond selecting equipment with suitable insulation voltage ratings.
- For example, 600/1000 V cables on a 230/400 V installation.
- The inspector should check this has been done.
Why the others are wrong:
B: SPDs address transient overvoltages, not these temporary overvoltages.
C: that relates to HV system faults with private substations.
D: GN3 does not require this.
Memory trick:
Loss of neutral? Check the cable voltage rating.