2391-50: Requirements and certification practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

68 of our 320 Initial Verification (2391-50) questions are on requirements and certification, about 21% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our requirements and certification questions test most often. Know where these are in your book before the exam.

  • 644.4 · 4 questions
  • 514.9 · 2 questions
  • 644.1 · 2 questions
  • 114.1 · 1 questions
  • 311.1 · 1 questions
  • 312.2 · 1 questions
  • 411.3 · 1 questions
  • 422.1 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. When entering the installation reference method for a circuit on a MEIWC or schedule of circuit details, where is the method taken from?

Show answer

Answer: D. Table 4A2 in Appendix 4 of BS 7671

  • GN3: the reference method is identified according to Table 4A2 in Appendix 4 of BS 7671.
  • The A4 MEIWC repeats this in its footnote to the reference method box.

The reference method links the cable to its current-carrying capacity.

Why the others are wrong:

A: that table gives maximum Zs for circuit-breakers.

B: that table gives minimum insulation resistance values.

C: the checklist lists inspection items, not installation methods.

Memory trick:

Reference method? Appendix 4, Table 4A2.

Reg Appendix 6 (MEIWC Section C); GN3 5.6

Q2. An employee of an electrical contractor signs an EIC for work carried out by the firm. What must they also make clear on the form?

Show answer

Answer: A. The company they are signing on behalf of

  • Appendix 6: when making out and signing a form on behalf of a company or other business, individuals should state for whom they are acting.
  • The EIC has a 'For/on behalf of' entry for each signatory.

This makes it clear which business takes responsibility for the work.

Why the others are wrong:

B: the form asks who the signatory acts for, not their private address.

C: insurance details are not part of the signatory particulars on the model form.

D: a VAT number is not asked for on the model certificate.

Memory trick:

Sign for a firm? Name the firm.

Reg Appendix 6 Introduction

Q3. A newly qualified electrician asks which regulation of the Electricity at Work Regulations 1989 requires persons to be competent to prevent danger and injury. Which one is it?

Show answer

Answer: A. Regulation 16

  • BS 7671 Part 2, note to the definition of Person: Regulation 16 of the EAWR requires persons to be competent to prevent danger and injury
  • HSE publication HSR25 gives guidance on this
  • BS 7671 links this to the defined terms skilled and instructed person

If you are not competent for a task, Regulation 16 means you must not do it unless suitably supervised.

Why the others are wrong:

B: Regulation 4(2) is about maintaining systems so as to prevent danger, not personal competence.

C: Regulation 4(3) concerns carrying out work activities safely, not the competence of the person.

D: Regulation 14 deals with work on or near live conductors, not competence.

Memory trick:

Sixteen: old enough to be competent.

Find it in the book

BS 7671:2018+A4:2026, page 44

Reg Part 2 (Person, Note 2)

Q4. In an office, the designer omits 30 mA RCD protection from some socket-outlets on the basis of a written risk assessment. How is this shown on the EIC?

Show answer

Answer: B. As a permitted exception under design, risk assessment attached

  • The A4 EIC design section has 'Details of permitted exceptions (Regulation 411.3.3)', and a suitable risk assessment must be attached.
  • GN3: the inspector is not to approve the assessment but should see that it exists, and it should be attached to the EIC or MEIWC for future reference.

The decision is the designer's, so it sits in the design section.

Why the others are wrong:

A: the design section has its own entry for permitted exceptions under 411.3.3.

C: classification codes are used on EICRs, not on EICs.

D: that section is for defects found in existing work during an addition.

Memory trick:

Design decision, design section, paperwork stapled on.

Reg 411.3.3; Appendix 6 (EIC Section C); GN3 2.5.2 h(v)

Q5. Regulation 641.6 requires initial verification to be made by skilled persons competent in such work. Which description matches a skilled person (electrically) in BS 7671?

Show answer

Answer: D. Adequate education, training and skills to perceive risks and avoid hazards

  • Skilled person (electrically): adequate education, training and practical skills, able to perceive risks and avoid hazards electricity can create
  • Instructed person: adequately advised or supervised by a skilled person
  • Ordinary person: neither skilled nor instructed

Only skilled persons may carry out and sign for verification (Regulation 641.6).

Why the others are wrong:

A: the definition is about education, training and practical skills together, not a single certificate.

B: that is the definition of an instructed person.

C: registration may be used to demonstrate competence, but it is not the BS 7671 definition.

Memory trick:

Skilled sees the risk; instructed is told about it.

Find it in the book

BS 7671:2018+A4:2026, page 44

Reg 641.6; Part 2

Q6. For a new dwelling, what does NHBC guidance recommend, as noted in GN3's section on record-keeping?

Show answer

Answer: B. All instructions for services are passed to the building owner

  • GN3 1.6: for domestic installations, NHBC guidance recommends that all instructions for services are passed to the building owner.
  • For non-domestic work, the CDM health and safety file plays a similar role.

Insurance requirements may also imply or specify records.

Why the others are wrong:

A: the recommendation is to hand them to the owner, not keep them.

C: the guidance is about passing them to the owner, not where to stick them.

D: the owner is the person who receives them.

Memory trick:

New home, new owner, all the instructions.

Reg GN3 1.6

Want 314 more 2391-50 questions? Start a free timed mock.