Q1. Which of these may pass through an opening in a cavity barrier, according to Approved Document B?
Show answer
Answer: D. Cables, or conduits containing cables
- AD B 5.24 limits openings in cavity barriers to:
- fire doorsets (minimum E 30)
- pipes following Section 9
- cables or conduits containing one or more cables
- openings with a fire damper
- fire resisting ducts, or ducts fitted with a fire damper
The opening around the cable should still be kept small and sealed.
Why the others are wrong:
A: openings are limited to specific items; spare unsealed gaps are not one of them.
B: ducts and openings need fire resistance or a suitable fire damper.
C: doors in cavity barriers must be fire doorsets of at least E 30.
Memory trick:
Cables can cross the barrier; open gaps cannot.