Q1. A PEX system is tested using Test B at 9 bar. After 30 minutes of pumping the gauge is noted at 9.0 bar. Thirty minutes after that it reads 8.6 bar, and 150 minutes after the noted reading it reads 8.3 bar. No leaks are seen. What is the result?
Show answer
Answer: B. Pass, as both pressure drops are within the limits
- Sch 2 para 12(2)(b) Test B: after 30 minutes pumping, note the pressure; the drop must be less than 0.6 bar after the next 30 minutes, or 0.8 bar after the next 150 minutes, with no visible leakage.
- 9.0 to 8.6 = 0.4 bar (under 0.6). 9.0 to 8.3 = 0.7 bar (under 0.8).
Both readings are inside the limits, so the system passes.
Why the others are wrong:
A: Test B allows a small drop; it does not require the pressure to hold exactly.
C: 0.5 bar is not a Test B limit; the limits are 0.6 and 0.8 bar.
D: 0.6 bar is the 30 minute limit; after 150 minutes the limit is 0.8 bar.
The maths
Noted pressure = 9.0 bar
Drop after 30 min = 9.0 - 8.6 = 0.4 bar (limit 0.6): OK
Drop after 150 min = 9.0 - 8.3 = 0.7 bar (limit 0.8): OK
No visible leakage: PASS
Memory trick:
Test B: 0.6 at half an hour, 0.8 at two and a half.