Q1. A water undertaker serves notice that backflow protection is needed on the incoming supply to a unit on an industrial estate, covering the whole site. Which statement about this whole-site protection is correct?
Show answer
Answer: B. The undertaker can require it by notice for all or part of premises
- Sch 2 para 15(4)(b): protection is needed where the water undertaker has given notice that it is required for the whole or part of any premises.
- This allows whole-site protection at the incoming supply and zone protection for part of a site.
- Para 15(1) still requires protection at each appliance, fitting or process.
Whole-site and zone protection are extra layers, not replacements.
Why the others are wrong:
A: the requirement comes from the undertaker's notice, not the occupier's request.
C: para 15(1) still requires adequate devices against backflow from each appliance, fitting or process.
D: the provision applies to any premises, and is most common on commercial and industrial sites.
Memory trick:
Whole site or zone: the undertaker can call for it by notice.