Q1. A water undertaker serves notice that backflow protection is needed on the incoming supply to a unit on an industrial estate, covering the whole site. Which statement about this whole-site protection is correct?

Show answer

Answer: B. The undertaker can require it by notice for all or part of premises

  • Sch 2 para 15(4)(b): protection is needed where the water undertaker has given notice that it is required for the whole or part of any premises.
  • This allows whole-site protection at the incoming supply and zone protection for part of a site.
  • Para 15(1) still requires protection at each appliance, fitting or process.

Whole-site and zone protection are extra layers, not replacements.

Why the others are wrong:

A: the requirement comes from the undertaker's notice, not the occupier's request.

C: para 15(1) still requires adequate devices against backflow from each appliance, fitting or process.

D: the provision applies to any premises, and is most common on commercial and industrial sites.

Memory trick:

Whole site or zone: the undertaker can call for it by notice.

Reg Water Fittings Regs Sch 2 para 15(4)(b)

Q2. Which of these fluids falls into fluid category 3?

Show answer

Answer: A. Water mixed with a chlorine-based disinfectant

  • Category 3 examples in Schedule 1: sodium hypochlorite (chloros and common disinfectants), ethylene glycol and copper sulphate solution.
  • Herbicides and pesticides are category 4; butchery waste is category 5; hot water is category 2.

Matching the fluid to the Schedule 1 examples is the first step in choosing protection.

Why the others are wrong:

B: herbicides are named as a category 4 example.

C: butchery and animal waste are category 5.

D: heated water with nothing added is category 2.

Memory trick:

Bleach is cat 3: slightly harmful, not seriously.

Reg Water Fittings Regs Sch 1, fluid category 3

Q3. When is a backflow prevention device treated as 'adequate' under Schedule 2?

Show answer

Answer: C. When it meets a regulator-approved specification

  • Sch 2 para 15(5): a device is adequate if it is in accordance with a specification approved by the regulator.
  • Para 7(3) separately requires concealed fittings and mechanical backflow devices to be gunmetal or dezincification resistant.

Adequacy is about meeting the approved specification for the risk.

Why the others are wrong:

A: ten working days is the consent period for notified work.

B: that is the pressure-withstand requirement for fittings, not the adequacy test for backflow devices.

D: that is a material requirement for concealed fittings and mechanical devices, not what makes a device adequate.

Memory trick:

Adequate means approved by the regulator's spec.

Reg Water Fittings Regs Sch 2 para 15(5)

Q4. In a house, a vented hot water cylinder is fed from a cold water storage cistern. When does Schedule 2 not require a backflow device for that cylinder?

Show answer

Answer: D. When the water in the cistern does not exceed 25°C

  • Sch 2 para 15(2): para 15(1) does not apply to a vented storage vessel supplied from a storage cistern, or a water heater whose expanded water may flow back into a supply pipe.
  • Condition: water in the cistern or supply pipe must not exceed 25°C.

The 25°C figure also appears in para 9 as the limit for cold pipes.

Why the others are wrong:

A: the exemption temperature is 25°C, not 60°C.

B: 230 litres is the notifiable bath size, not a backflow exemption.

C: a relief valve deals with overheating, not backflow, and is not the exemption condition.

Memory trick:

Keep the cold side under 25 and the cylinder needs no backflow device.

Reg Water Fittings Regs Sch 2 para 15(2)

Q5. Water drawn from the hot tap of a domestic hot water system has been heated but nothing has been added to it. Which fluid category applies?

Show answer

Answer: A. Fluid category 2

  • Category 2: category 1 water whose aesthetic quality is impaired by a change in temperature or by substances changing taste, odour or appearance.
  • Schedule 1 specifically includes water in a hot water distribution system.

Heated but otherwise untouched water is category 2.

Why the others are wrong:

B: once wholesome water's temperature has changed it is no longer category 1.

C: category 3 needs low toxicity substances in the water; heating alone does not create a health hazard.

D: category 5 involves pathogens or very toxic substances, not simply heated water.

Memory trick:

Warmed or a bit off in taste or look: cat 2.

Reg Water Fittings Regs Sch 1, fluid category 2

Q6. A farm has its own borehole supply as well as a mains supply. Which Schedule 2 requirement still applies to the borehole fittings even though they are not connected to the mains?

Show answer

Answer: D. Prevention of cross connection to unwholesome water

  • Reg 2(3): the Regulations do not apply to fittings not connected to undertaker water, except for paragraph 14 of Schedule 2.
  • Para 14 covers prevention of cross connection to unwholesome water, including identifying such pipework.

Borehole pipework must be marked and must never be connected to the mains without proper backflow protection.

Why the others are wrong:

A: this does not apply to fittings with no connection to the undertaker's water.

B: the pressure test only applies to fittings connected to the undertaker's supply.

C: the cistern requirements only apply to fittings on the undertaker's supply.

Memory trick:

Private supply? Only the cross-connection rule follows it.

Reg Water Fittings Regs reg 2(3) and Sch 2 para 14