QELTK3/006: Testing practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

88 of our 180 Inspection, Testing, Commissioning and Certification (QELTK3-006) questions are on testing, about 49% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our testing questions test most often. Know where these are in your book before the exam.

  • 643.7 · 12 questions
  • 643.3 · 9 questions
  • 643.2 · 8 questions
  • 643.6 · 6 questions
  • 643.1 · 4 questions
  • 643.8 · 4 questions
  • 643.9 · 4 questions
  • 411.5 · 3 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Why must the prospective fault current be found at the origin of the installation?

Show answer

Answer: C. To check devices can withstand the fault current

  • The prospective fault current at the origin is used to make sure switchgear and protective devices can withstand it under fault conditions.
  • A device with too low a breaking capacity could fail violently.

Know the worst fault so your devices can handle it.

Why the others are wrong:

A: RCDs are rated by residual current, not fault current.

B: voltage drop uses design current.

D: test voltage depends on circuit voltage.

Memory trick:

PFC tells you how tough your breakers must be.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 294

Reg 643.7.3.201; EAL Ch4

Q2. At the origin, the supply voltage is 230 V and the measured loop impedance is 0.25 ohm. Using Ohm's law, what is the prospective fault current?

Show answer

Answer: B. 920 A

  • Prospective fault current I = U / Z.
  • 230 / 0.25 = 920 A.

This value is needed to check the breaking capacity of protective devices.

Why the others are wrong:

A: this multiplies instead of dividing.

C: the decimal place is wrong.

D: this is ten times too large.

The maths

I = U / Z
I = 230 / 0.25
I = 920 A

Memory trick:

Volts over ohms gives fault amps.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 294

Reg 643.7.3.201; EAL Ch4

Q3. At a commercial distribution board the prospective fault current is measured as 7.2 kA. The circuit-breakers are rated 6 kA and there is no upstream back-up protection arranged. What is the position?

Show answer

Answer: A. Unsuitable: 6 kA is below the fault current

  • Each protective device must have a breaking capacity not less than the prospective fault current where it is installed.
  • 6 kA is below 7.2 kA.
  • GN3 says to consider any current-limiting effect of upstream devices before recording a defect, but none is arranged here.

Higher-rated devices or proper back-up protection are needed.

Why the others are wrong:

B: the breaking capacity must not be less than the prospective fault current at the point of installation.

C: the larger of the short-circuit and earth fault currents is used.

D: an RCD does not raise the breaking capacity of the circuit-breakers.

Memory trick:

Breaking capacity must beat the fault current, not the other way round.

Find it in the book

IET Guidance Note 3 (2022 edition), page 89

Reg 434.5.1; 643.7.3.201

Q4. A 32 A Type B ring final circuit has r1 = 0.60 Ω and r2 = 1.00 Ω. Ze is 0.30 Ω. What is the calculated Zs, and does it meet the 80 % rule against the Table 41.3 value of 1.37 Ω?

Show answer

Answer: B. 0.70 Ω, which is below the 1.10 Ω limit

  • R1 + R2 = (r1 + r2) / 4 = 1.60 / 4 = 0.40 Ω.
  • Zs = Ze + (R1 + R2) = 0.30 + 0.40 = 0.70 Ω.
  • 80 % of 1.37 Ω = 1.10 Ω, so the circuit complies.

The 80 % rule allows for conductors being cooler at test than at full operating temperature.

Why the others are wrong:

A: this adds the full end-to-end r1 and r2 to Ze instead of (r1 + r2) / 4.

C: this is R1 + R2 alone; Ze must be added to give Zs.

D: 0.55 Ω is 40 % of 1.37 Ω; the rule of thumb uses 80 %, giving about 1.10 Ω.

The maths

R1 + R2 = (0.60 + 1.00) / 4 = 0.40 Ω
Zs = 0.30 + 0.40 = 0.70 Ω
Limit = 0.8 x 1.37 = 1.10 Ω
0.70 < 1.10, so it complies

Memory trick:

Ring: quarter the loop, add Ze, compare with 80 %.

Find it in the book

IET Guidance Note 3 (2022 edition), page 66; BS 7671:2018+A4:2026, page 75

Reg 643.7.3; Table 41.3

Q5. When current flows from an earth electrode into the ground, the voltage around it falls off like ripples on a pond. Within what distance does the book say it falls to a safe level?

Show answer

Answer: D. About 2 to 3 m

  • The voltage at an earth electrode radiates outwards like ripples from a pebble thrown into a pond.
  • It falls to a safe level within the first 2 or 3 m of the electrode.

The area of soil that really matters for an electrode is close around it.

Why the others are wrong:

A: this is far too long.

B: this is too short.

C: this is too long.

Memory trick:

Ripples die in two or three metres.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 289

Reg EAL Ch4 earth electrode

Q6. A 100 mA time-delayed S type RCD is tested at its rated residual current and trips in 95 ms. What is the result?

Show answer

Answer: A. It fails, as an S type should take at least 130 ms

  • BS 7671 gives S type RCDs a window at IΔn of 130 ms minimum to 500 ms maximum.
  • 95 ms is too fast.
  • The time delay exists so a downstream general RCD can clear a fault first.

The device should be investigated and probably replaced.

Why the others are wrong:

B: 300 ms is the limit for general non-delay types; S types have their own window.

C: it must also be no quicker than the 130 ms minimum.

D: an S type that trips too quickly loses its delay and will not discriminate with downstream RCDs.

Memory trick:

S type: not before 130, not after 500.

Find it in the book

BS 7671:2018+A4:2026, page 251

Reg 643.7.1 Note

Want 174 more QELTK3/006 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.