Q1. A circuit is wired in single-core cables, with the line conductor in one steel conduit and the neutral in a separate steel conduit. Why does this fail inspection?
Show answer
Answer: B. Line and neutral must share the same steel conduit
- GN3's rigid metal conduit checklist says line, neutral and any protective conductors must be contained in the same conduit (521.5.1).
- Splitting them causes electromagnetic effects: the steel around a single conductor sets up eddy currents and heating.
- The A4 schedule also lists protection against electromagnetic effects where cables enter ferromagnetic enclosures.
Keep go and return together so their magnetic fields cancel.
Why the others are wrong:
A: single-core cables in steel conduit are a common, permitted wiring system.
C: there is no such rule; the problem is splitting the circuit between enclosures.
D: this misses the point; separating the conductors is what causes the problem.
Memory trick:
Go and return travel together in steel.
Find it in the book
IET Guidance Note 3 (2022 edition), page 51; BS 7671:2018+A4:2026, page 148