QELTK3/006: Inspection practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

30 of our 180 Inspection, Testing, Commissioning and Certification (QELTK3-006) questions are on inspection, about 17% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our inspection questions test most often. Know where these are in your book before the exam.

  • 642.3 · 8 questions
  • 411.3 · 1 questions
  • 416.2 · 1 questions
  • 422.2 · 1 questions
  • 514.10 · 1 questions
  • 514.3 · 1 questions
  • 521.10 · 1 questions
  • 521.5 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A circuit is wired in single-core cables, with the line conductor in one steel conduit and the neutral in a separate steel conduit. Why does this fail inspection?

Show answer

Answer: B. Line and neutral must share the same steel conduit

  • GN3's rigid metal conduit checklist says line, neutral and any protective conductors must be contained in the same conduit (521.5.1).
  • Splitting them causes electromagnetic effects: the steel around a single conductor sets up eddy currents and heating.
  • The A4 schedule also lists protection against electromagnetic effects where cables enter ferromagnetic enclosures.

Keep go and return together so their magnetic fields cancel.

Why the others are wrong:

A: single-core cables in steel conduit are a common, permitted wiring system.

C: there is no such rule; the problem is splitting the circuit between enclosures.

D: this misses the point; separating the conductors is what causes the problem.

Memory trick:

Go and return travel together in steel.

Find it in the book

IET Guidance Note 3 (2022 edition), page 51; BS 7671:2018+A4:2026, page 148

Reg 521.5.1

Q2. Two pendant flexes have been connected to one standard ceiling rose to feed two lampholders. What should the inspector find?

Show answer

Answer: A. Non-compliant, unless the rose is made for multiple pendants

  • Regulation 559.5.1.202 says a ceiling rose must not be used for attaching more than one outgoing flexible cable unless it is specially designed for multiple pendants.
  • GN3's lighting points checklist repeats this.
  • Two flexes in one terminal can work loose and the rose may not support the extra mass.

One rose, one flex, unless the rose is made for more.

Why the others are wrong:

B: flex size does not matter; a standard rose must not have more than one outgoing flex.

C: load is not the issue; the rose is not designed for two flexes.

D: a ceiling rose with one pendant flex is a normal, permitted arrangement.

Memory trick:

One rose, one flex.

Find it in the book

IET Guidance Note 3 (2022 edition), page 49; BS 7671:2018+A4:2026, page 233

Reg 559.5.1.202

Q3. Which of these is NOT a factor the book lists when deciding the size of the sample for a periodic inspection?

Show answer

Answer: C. The number of people living in the building

  • Factors for sampling: previous certificates, age and condition, evidence of maintenance, time since last inspection, and size of the installation.
  • Engineering judgement is needed.

The less you know and the worse it looks, the bigger the sample.

Why the others are wrong:

A: this is a listed factor.

B: this is a listed factor.

D: this is a listed factor.

Memory trick:

Paper, age, care, time, size.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 274

Reg GN3 3.8; EAL Ch4 sampling

Q4. Why should an inspector think carefully before disconnecting cables to carry out a test during a periodic inspection?

Show answer

Answer: B. Reassembly may be unsatisfactory, so the risk must be justified

  • Dismantling, and especially disconnecting cables and components, introduces the risk of unsatisfactory reassembly.
  • The tester should consider whether the risk is justified.

Every termination you undo is one you might redo badly.

Why the others are wrong:

A: it does not invalidate the report.

C: disconnection is not prohibited.

D: they can still be tested.

Memory trick:

Undo it only if it is worth redoing.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 273

Reg EAL Ch4 periodic inspection

Q5. A separate single-pole switch has been fitted in the circuit protective conductor of a machine circuit so that the earth can be disconnected during maintenance. What should the inspector conclude?

Show answer

Answer: A. Not permitted: a separate switch must not break the cpc

  • Regulation 543.3.3.101 says no switching device shall be inserted in a protective conductor, apart from limited exceptions.
  • GN3 notes BS 7671 does not allow a switching or isolating device in the earth or protective conductor, other than a plug and socket-outlet, except in the special conditions of 543.3.3.101.
  • A separate switch in the cpc could leave the machine energized with no earth.

The cpc must always be there when the live conductors are connected.

Why the others are wrong:

B: isolation is of live conductors; breaking the cpc removes fault protection.

C: locking does not make it permissible to switch the protective conductor.

D: the rule applies whatever the system earthing arrangement.

Memory trick:

Switch the lines, never the earth.

Find it in the book

IET Guidance Note 3 (2022 edition), page 40; BS 7671:2018+A4:2026, page 213

Reg 543.3.3.101

Q6. You are asked to inspect a shop with no previous certificates. The wiring looks neglected and abused. What sample size is appropriate?

Show answer

Answer: D. A much larger proportion, possibly 100%

  • With no previous certificates and an installation that looks abused, a larger percentage must be inspected and tested, in some cases 100%.
  • The extent of sampling must be agreed with the person ordering the work.

Less history and worse condition mean more inspection.

Why the others are wrong:

A: there is no fixed standard sample, and here it should be larger.

B: poor condition means more should be inspected, not less.

C: inspecting only the board would miss defects in circuits.

Memory trick:

No history plus bad looks equals look at everything.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 274

Reg GN3 3.8; EAL Ch4 sampling

Want 174 more QELTK3/006 questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other QELTK3/006 topics

Revise this topic