Q1. Which job does NOT need Gas Safe registration, although the person must still be competent?

Show answer

Answer: A. Swapping an empty LPG cylinder for a full one

  • Gas storage vessels are not gas fittings, so changing cylinders does not require Gas Safe registration.
  • People doing it still need competence and must follow supplier or manufacturer instructions.

Installing or replacing a tank that involves work on service pipework or other fittings needs a registered engineer.

Why the others are wrong:

B: work on installation pipework needs Gas Safe registration.

C: the guidance says this involves gas fittings and needs a registered engineer.

D: work on a gas appliance needs an HSE-approved class of persons.

Memory trick:

Cylinder swap: competent. Pipework: registered.

Find it in the book

HSE L56 (5th edition, 2018), page 24

Reg Gas Safety (Installation and Use) Regulations 1998, regulation 3(3) to (4); HSE L56 guidance paragraphs 95 to 96

Q2. Which type of gas appliance may be installed in a bathroom or shower room?

Show answer

Answer: C. Only a room-sealed appliance

  • Regulation 30(1): no gas appliance may be installed in a bathroom or shower room unless it is room-sealed.
  • This includes a cupboard in the room, or a cupboard next to it that has an air vent into the room.

Different rules apply to rooms used for sleeping.

Why the others are wrong:

A: a cut-out does not make an appliance room-sealed.

B: the 14 kW rule applies to sleeping rooms, not bathrooms.

D: a flueless heater is not room-sealed, alarm or not.

Memory trick:

Bathroom gas? Room-sealed only.

Find it in the book

HSE L56 (5th edition, 2018), page 59

Reg Gas Safety (Installation and Use) Regulations 1998, regulation 30(1)

Q3. A Gas Safe engineer needs to use a blowtorch on pipework that has contained gas. What does the guidance advise?

Show answer

Answer: A. Isolate the supply and purge the gas before using the torch

  • Regulation 6(4): no one exposing gasways that contain or have contained gas may use a source of ignition that could cause fire or explosion.
  • Sources of ignition include blow-lamps and hot-air guns; gasways should generally be purged of gas before using a blow torch.

A safe system of work includes effective isolation of the gas supply.

Why the others are wrong:

B: moving the flame does not remove the risk of fire or explosion.

C: ventilation alone is not the safe system described; the gasway should be purged.

D: the guidance lists hot-air guns as sources of ignition.

Memory trick:

Purge before you play with fire.

Find it in the book

HSE L56 (5th edition, 2018), page 28

Reg Gas Safety (Installation and Use) Regulations 1998, regulation 6(4); HSE L56 guidance paragraph 120

Q4. After work that might affect the gas tightness of an installation, how far must it be tested?

Show answer

Answer: C. At least to the nearest valves upstream and downstream

  • Regulation 6(6): after work that might affect gas tightness, test immediately, at least as far as the nearest valves upstream and downstream.
  • In homes the test normally covers pipework from the meter or emergency control valve to the appliance shut-off device.

This test is also called a soundness or pressure decay test.

Why the others are wrong:

A: the minimum is the nearest valves either side of the work.

B: the test must reach the nearest valve upstream as well.

D: the regulation requires a wider test than the joints alone.

Memory trick:

Valve to valve, straight after the work.

Find it in the book

HSE L56 (5th edition, 2018), page 29

Reg Gas Safety (Installation and Use) Regulations 1998, regulation 6(6); HSE L56 guidance paragraph 125

Q5. A neighbour asks you to swap their gas hob as a favour. You are a plumber but not Gas Safe registered. What is the legal position?

Show answer

Answer: C. Anyone doing gas work must be competent, paid or not

  • Regulation 3(1): no person may work on a gas fitting unless they are competent to do so.
  • The guidance says DIY gas engineers and people doing favours for friends and relatives must still be competent.

A business doing gas work must also be a member of an HSE-approved class of persons, which at publication meant Gas Safe Register.

Why the others are wrong:

A: the like-for-like exceptions only cover certain hose and regulator replacements, not appliances.

B: the guidance says people doing favours for friends and relatives still need to be competent.

D: isolating the supply does not make an unqualified person competent to do gas work.

Memory trick:

Paid or unpaid, gas work needs a competent person.

Find it in the book

HSE L56 (5th edition, 2018), page 23

Reg Gas Safety (Installation and Use) Regulations 1998, regulation 3(1); HSE L56 guidance paragraph 83

Q6. HSE defines hot work as any process that generates flame, sparks or heat. Which plumbing task counts as hot work?

Show answer

Answer: A. Using an electric soldering iron or heat gun

  • Hot work is any process that generates flame, sparks or heat.
  • HSE lists soldering irons and heat guns, grinding and cutting metal, and oxy-fuel work as common hot works.

Electric tools can still be hot work if they produce heat.

Why the others are wrong:

B: a hand cutter is a cold cutting method.

C: tightening a compression joint does not generate flame, sparks or heat.

D: push-fit is a cold method that produces no flame, sparks or heat.

Memory trick:

Flame, spark or heat: it's hot work.

Find it in the book

HSE HSG168 (3rd edition, 2022), page 24

Reg HSE HSG168, paragraphs 118 and 120

Want 194 more CITB Plumbing (JIB) questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other CITB Plumbing (JIB) topics

Free official guides for this topic

Our questions are written from these documents. Download them free to revise from the source.

© Crown copyright (HSE). Unchanged copies, reproduced under the Open Government Licence v3.0. FreeMocks is not connected to or endorsed by HSE or the government.

Revise this topic