PAT 2377-77: Test instruments and electrical tests practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

49 of our 150 In-Service Inspection and Testing of Electrical Equipment (PAT) (2377-77) questions are on test instruments and electrical tests, about 33% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. An older appliance's fuse does not match current Table 10.6 values but met the BS 1363 edition in force when made. What does the Code say?

Show answer

Answer: B. Standards are not retrospective, so it need not be changed

  • Older editions: 3 A for 0.5 mm2, 13 A above 0.5 mm2
  • High inrush: 5 A on 0.5 mm2 was allowed
  • British Standards are not retrospective

Check the manufacturer's requirements first.

Why the others are wrong:

A: products that met the standard at manufacture need not change.

C: no change is needed if it complied when made.

D: the inspector checks manufacturer advice but no return is needed.

Memory trick:

Built to the old book, judged by the old book.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 80

Reg CoP 10.14.1

Q2. An unmarked heater's class cannot be identified from its construction. How should it be treated for testing?

Show answer

Answer: B. As Class I

  • Unknown class: treat as Class I
  • The manufacturer can advise the type and tests

This makes sure the earth path is checked rather than missed.

Why the others are wrong:

A: assuming Class II would skip the earth continuity test.

C: Class III is SELV equipment, not the default.

D: the Code gives a default class instead.

Memory trick:

When in doubt, earth it out: Class I.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 68

Reg CoP 10.2

Q3. A tester shows an insulation resistance of 2.5 MOhm. What is this in ohms?

Show answer

Answer: B. 2,500,000 Ohm

  • Mega means 1,000,000
  • 2.5 x 1,000,000 = 2,500,000 Ohm

Convert to base units before any calculation.

Why the others are wrong:

A: that would be 2.5 kOhm, multiplying by only 1,000.

C: this multiplies by ten million, not one million.

D: this divides instead of multiplying, as for milli.

The maths

2.5 MOhm x 1,000,000 = 2,500,000 Ohm

Memory trick:

Mega = million: multiply by 1,000,000.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 124

Reg CoP Appendix 8, A8.7, Table A8.1

Q4. An extension lead will power a drill in a workshop where mechanical damage is likely. What protection does the Code say it must have?

Show answer

Answer: C. An RCD

  • Where use or environment raises shock risk, such as workshops or outdoors
  • Any extension lead supplying equipment must be RCD protected
  • Plug-in RCDs may be needed in older buildings

Don't assume older sockets have RCDs.

Why the others are wrong:

A: a metal drum would make it Class I, not safer.

B: a small fuse does not address shock risk.

D: the requirement given is RCD protection.

Memory trick:

Rough place, RCD in place.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 75

Reg CoP 10.10

Q5. A vacuum cleaner has 8 m of 1.0 mm2 flex (19.5 mOhm/m). Continuity from its metal parts to the plug earth pin reads 0.30 Ohm. What should the inspector conclude?

Show answer

Answer: B. It exceeds the 0.256 Ohm limit and fails

  • R = 19.5 x 8 / 1,000 = 0.156 Ohm
  • Limit = 0.1 + 0.156 = 0.256 Ohm

A reading of 0.30 Ohm is higher than the limit, so the item fails.

Why the others are wrong:

A: this adds 0.2 Ohm instead of 0.1 Ohm.

C: 0.5 Ohm is only for older items where the design explains it.

D: 0.156 Ohm is just the flex resistance, without the 0.1 Ohm.

The maths

R = (19.5 x 8) / 1,000 = 0.156 Ohm
Limit = 0.1 + 0.156 = 0.256 Ohm
0.30 Ohm > 0.256 Ohm, so fail

Memory trick:

mOhm/m x m / 1,000 + 0.1 = limit.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 71

Reg CoP 10.5.2, Table 10.1; Appendix 5, Table A5.1

Q6. For in-service testing of a 30 mA RCD used for shock protection, what is the required performance check?

Show answer

Answer: A. Trips within 40 ms at 5 x IΔn with no load connected

  • Test at 5 x IΔn (150 mA for 30 mA)
  • Must operate within 40 ms
  • No load connected
  • Also check the RCD test button works during functional checks

Other settings exist but are not needed for in-service testing.

Why the others are wrong:

B: the in-service check is at 5 x IΔn, with no load.

C: that is a no-trip test not required for in-service work.

D: the time at 5 x IΔn is 40 ms and no load is connected.

Memory trick:

Five times, forty milliseconds, no load.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 66

Reg CoP 9.5

Want 144 more PAT 2377-77 questions? Start a free timed mock.