PAT 2377-77: Equipment scope and classification practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

25 of our 150 In-Service Inspection and Testing of Electrical Equipment (PAT) (2377-77) questions are on equipment scope and classification, about 17% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Two enclosures are rated IP5X and IP6X. What is the difference in protection against solids?

Show answer

Answer: A. IP5X is dust protected; IP6X is dust tight

  • First numeral 5 = dust protected.
  • First numeral 6 = dust tight.
  • Both protect against access to hazardous parts with a wire.

Higher number means better protection.

Why the others are wrong:

B: this reverses them; 6 is the higher rating, dust tight.

C: 2.5 mm is numeral 3 and 1.0 mm is numeral 4.

D: tool is numeral 3 and finger is numeral 2.

Memory trick:

Five lets a bit in; six is tight as a fix.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 95

Reg App 2, Table A2.1

Q2. A dental practice asks you to PAT test its ultrasound machine, which requires testing to BS EN 62353. What is the position under this CoP?

Show answer

Answer: A. It is outside the scope of this CoP

  • Sensitive medical equipment (ECG, infusion pump, ultrasound, X-ray) should be tested only by a competent person familiar with BS EN 62353.
  • Equipment requiring testing to BS EN 62353 is outside the scope of this CoP.

Medical equipment is also listed in Section 4.4 as out of scope.

Why the others are wrong:

B: equipment needing testing to BS EN 62353 is outside the scope of this CoP.

C: the classification is not the issue; the item is outside scope.

D: the CoP does not cover it; a competent person familiar with BS EN 62353 should test it.

Memory trick:

Medical kit: wrong code, wrong book.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 16

Reg CoP 1.4

Q3. An isolating transformer provides electrical separation. Which arrangement does the CoP say should NOT be used with it?

Show answer

Answer: D. Supplying Class II FE equipment

  • Electrical separation can supply one Class I item or any number of Class II items.
  • More than one Class I item needs strict controls, as faults may go undetected.
  • It should not be used with equipment needing a functional earth, such as Class II FE.

The shaver socket is the everyday example.

Why the others are wrong:

A: this is the common example of electrical separation.

B: this is permitted.

C: any number of Class II items may be supplied.

Memory trick:

Separated means no earth, so no FE kit.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 54

Reg CoP 6.4

Q4. An older laptop power supply is marked "ITE" and has a three-core lead. What classification does the CoP use for it, and how should it be tested?

Show answer

Answer: C. Class II FE, tested as Class II

  • Equipment previously marked ITE is now called Class II FE.
  • It meets Class II for fault protection but needs a functional earth, usually for filter capacitors.
  • When inspecting and testing, treat it as Class II.

The newer symbol is the functional earth symbol inside the double-square.

Why the others are wrong:

A: it is a 230 V mains supply, not an SELV/ES1 product.

B: the CoP says these products should be treated as Class II when inspecting and testing, despite the functional earth.

D: Class 0I relates to Class I items with two-core cables and special plugs.

Memory trick:

FE = Filters need Earth, but it is still tested as Class II.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 52

Reg CoP 2, 6.3

Q5. A specialist heater is described by its maker as Class 0I. What does that pseudo-class mean?

Show answer

Answer: D. Class I item on two-core flex with a non-earth plug

  • Class 0I is not a defined class; it comes from a note in withdrawn BS 2754.
  • It is a Class I item allowed a two-core cable with a plug that cannot enter an earthed socket-outlet.
  • It is specialist equipment, only used with specific guidance.

In the UK it is allowed only in very specific locations.

Why the others are wrong:

A: that describes Class III/ES1.

B: that is Class II FE.

C: that is Class 0.

Memory trick:

0I: earthing parts, no earth wire.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 55

Reg CoP 6.6.2

Q6. An old set of series-connected Christmas lights uses bell-flex type cable that is insulated but not sheathed. How does the CoP classify this?

Show answer

Answer: D. Class 0, not acceptable in the UK

  • Class 0: protection relies on basic insulation only, with no earthing provision.
  • If basic insulation fails, reliance is placed on the environment.
  • The CoP's example is older series Christmas lights with insulated but unsheathed bell flex.
  • Class 0 is not acceptable in the UK.

Modern sheathed versions are deemed to meet Class II.

Why the others are wrong:

A: Class 0I is a Class I item with a two-core cable and special plug, not this.

B: there is no supplementary or reinforced insulation, so it is not Class II.

C: it is mains-powered with basic insulation only.

Memory trick:

Class 0 = zero back-up.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 54

Reg CoP 2, 6.6.1