Q1. What do the Electricity at Work Regulations say about how often portable equipment must be inspected and tested?

Show answer

Answer: C. No interval is set; it is needed where danger could arise

  • The EAWR do not prescribe how often equipment should be assessed.
  • They require it where danger could arise from a lack of maintenance.
  • Frequency depends on the likelihood of maintenance being needed and the consequences of not doing it.

There is no legal 'annual PAT'.

Why the others are wrong:

A: no frequency is prescribed by the EAWR for any type.

B: the EAWR do not prescribe any frequency.

D: the EAWR do not set this or any other interval.

Memory trick:

EAWR: no dates, just no danger.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 81

Reg CoP Section 11

Q2. Which of these is NOT one of the records the Code of Practice says should be established and maintained?

Show answer

Answer: C. A log of every user check carried out

  • Records to keep: a register of all equipment, a record of formal and combined inspections and tests, a repair or maintenance register and a test instrument log and calibration record.
  • User checks need no record unless something is unsatisfactory.

Four records: register, results, repairs, instruments.

Why the others are wrong:

A: this is one of the listed records.

B: an equipment register is one of the listed records.

D: this is one of the listed records.

Memory trick:

Register, Results, Repairs, Instruments.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 85

Reg CoP 12.1

Q3. Which fault is the Code of Practice clear that a properly done inspection can find but an electrical test may not?

Show answer

Answer: B. A cracked casing

  • Inspection can identify faults not apparent from electrical tests, such as a cracked case, a damaged flex or evidence of overheating.
  • Inspection should always precede testing, where testing is required.

Instruments can't see cracks.

Why the others are wrong:

A: this is found by an earth continuity test.

C: this is found by an insulation resistance test.

D: polarity is confirmed by a polarity test.

Memory trick:

Testers measure; eyes see cracks.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 82

Reg CoP 11.2

Q4. Following the Appendix 7 flowchart, a rack is in a controlled area used only by skilled staff, is rarely changed, is tidy, has no obvious wiring errors and has earth-leakage monitoring on its supply. What should follow?

Show answer

Answer: C. Visual inspection and thermal imaging

  • Controlled environment: yes. Changed often: no. Tidy: yes. Free of obvious errors: yes.
  • Earth-leakage monitoring fitted: yes, so proceed with visual inspection and thermal imaging.
  • Without monitoring, add earth bond integrity tests and insulation tests as required.

Monitoring reduces the need for intrusive testing.

Why the others are wrong:

A: this route applies if the rack is not in a controlled environment or is changed often.

B: this fuller set is for racks without earth-leakage monitoring.

D: this route is for racks with obvious wiring errors or broken equipment.

Memory trick:

Monitored and tidy: look and use the thermal camera.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 118

Reg Appendix 7, Figure A7.2

Q5. In the manufacturing example, why are the installed electrical accessories (roller-shutter controls, hand-dryers, alarm panel) left to the fixed wiring inspection every 5 years?

Show answer

Answer: B. Low risk, staff do user checks, and no staff can safely isolate them

  • Installed accessories: low risk, fixed in position, generally Class I, nothing failed to date.
  • No staff are trained to perform safe isolations or detailed inspection and testing.
  • Given the low risk and staff user checks, they come under the building fixed wiring inspection every 5 years.

Fixed, low-risk items can ride with the installation inspection.

Why the others are wrong:

A: they are generally Class I; the reasoning is low risk and staff skills.

C: the rolling IT contract applies to office equipment, not the accessories.

D: records show nothing has failed to date.

Memory trick:

Fixed and low risk: test with the building.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 127

Reg Appendix 9, Table A9.2

Q6. Which factor in a frequency risk assessment covers items with built-in batteries or IT kit that becomes obsolete?

Show answer

Answer: A. Functional in-service life

  • Factors to consider include environment, users, construction, type, frequency of use, installation method, previous records and functional in-service life.
  • Some equipment has an intentionally short life due to internal batteries or software obsolescence.

Short-life kit may be replaced before a long test interval comes round.

Why the others are wrong:

B: this covers how often the item is used, not its built-in service life.

C: this covers isolator position, cable management and protective devices.

D: this covers the class of equipment, such as Class I or II.

Memory trick:

Built-in batteries = built-in end date.

Find it in the book

IET Code of Practice for In-service Inspection and Testing of Electrical Equipment, 5th Edition, page 81

Reg CoP 11.1(h)