QELTK3/007: Rectification and causes of faults practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

30 of our 120 Fault Diagnosis and Rectification (QELTK3-007) questions are on rectification and causes of faults, about 25% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our rectification and causes of faults questions test most often. Know where these are in your book before the exam.

  • 525 · 2 questions
  • 314.1 · 1 questions
  • 643.1 · 1 questions
  • 643.2 · 1 questions
  • 643.3 · 1 questions
  • 643.9 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. After a replacement supply cable is fitted to a three-phase pump motor, the motor runs backwards. What is the correct fix?

Show answer

Answer: A. Swap any two line conductors at the motor

  • Wrong rotation means two line conductors are cross-connected.
  • Swapping any two reverses the phase sequence and the motor direction.
  • GN3 recommends checking phase rotation at the point closest to the load before it is energised.

A phase rotation tester confirms the change.

Why the others are wrong:

B: this would put a line conductor on the neutral and does not reverse a three-phase motor.

C: shifting all three round by one keeps the same sequence, so the motor still runs backwards.

D: volt drop does not change direction of rotation.

Memory trick:

Wrong way round? Swap any two.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 296; IET Guidance Note 3 (2022 edition), page 93

Reg 643.9

Q2. When re-terminating a damaged copper conductor, an apprentice reaches for an aluminium crimp lug of the right size. Why should you stop them?

Show answer

Answer: C. Dissimilar metal corrosion at the joint

  • When re-terminating, use the correct type and size of termination.
  • An aluminium crimp on a copper conductor can introduce dissimilar metal corrosion.
  • Corrosion raises resistance, which leads to heating and a repeat fault.

Match lug material to conductor material.

Why the others are wrong:

A: the lug does not cause tripping on its own.

B: the problem the book highlights is corrosion between the metals.

D: lug material must match the conductor, whatever the cable type.

Memory trick:

Copper on copper, aluminium on aluminium.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 322

Reg Fault correction

Q3. After a repair, the polarity test reveals a reversed connection. You correct it. Which tests must now be carried out?

Show answer

Answer: B. The polarity test and all the tests that came before it

  • If any test fails, that test and all preceding tests must be repeated once the fault is rectified.
  • The earlier results may have been influenced by the fault.

Only then move on to the remaining tests and functional checks.

Why the others are wrong:

A: earlier results may have been influenced by the fault, so they must be repeated too.

C: this skips re-checking earlier tests that the fault may have affected.

D: a functional test does not replace the required electrical tests.

Memory trick:

Fail one, redo it and everything before it.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 343

Reg 643.1

Q4. You have replaced a damaged section of cable on a lighting circuit with LED dimmers. The new cable was tested at 500 V before connection. Which insulation test should be made once the dimmers are reconnected?

Show answer

Answer: C. 250 V DC, live conductors linked to cpc, min 1 MΩ

  • Where equipment may be damaged by the test, cables are tested at 500 V before connection.
  • After connection, a 250 V DC test is made between live conductors connected together and the cpc.
  • The result must be at least 1 MΩ, and the test voltage is recorded.

This proves the repair without damaging electronics.

Why the others are wrong:

A: 1000 V is for circuits above 500 V and could destroy the dimmers.

B: this would apply full test voltage across the dimmers.

D: the test is to the cpc with live conductors linked, and 0.5 MΩ is the SELV/PELV value.

Memory trick:

Electronics on? Drop to 250 V, link L and N.

Find it in the book

IET Guidance Note 3 (2022 edition), page 71

Reg 643.3.3

Q5. Every connection must normally be accessible for inspection and testing. Which of these is an exception?

Show answer

Answer: C. A joint made with a compression tool

  • Connections must remain accessible for inspection, testing and maintenance.
  • Exceptions include compound-filled or encapsulated joints, cold tail to heating element connections, joints made by welding, brazing, soldering or compression tool, and maintenance-free (MF) accessories to BS 5733.

These joints are designed not to need maintenance.

Why the others are wrong:

A: ceiling rose terminals must stay accessible.

B: screw terminals in junction boxes must be accessible.

D: consumer unit terminals must be accessible.

Memory trick:

Crimped, soldered, sealed, MF: can be hidden.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 320

Reg BS 7671 526.3

Q6. A circuit-breaker trips the moment power is applied to a new machine, but tests show no short circuit or earth fault. What should be checked next?

Show answer

Answer: D. Whether the breaker suits the machine's demand

  • If no short circuit is apparent, compare the design current (including any starting current) with the breaker rating and type.
  • An unsuitable device can trip even though the circuit is healthy.

Any change must still provide correct protection for the cable.

Why the others are wrong:

A: insulation has already been tested and no fault was found.

B: cpc size does not cause a breaker to trip when no fault exists.

C: phase sequence affects rotation, not instant tripping.

Memory trick:

No fault found? Check device against demand.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 354

Reg Symptoms and corrective action

Want 114 more QELTK3/007 questions? Start a free timed mock.