QELTK3/007: Fault types, symptoms and test instruments practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

36 of our 120 Fault Diagnosis and Rectification (QELTK3-007) questions are on fault types, symptoms and test instruments, about 30% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our fault types, symptoms and test instruments questions test most often. Know where these are in your book before the exam.

  • 643.2 · 7 questions
  • 643.3 · 2 questions
  • 643.7 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Testing a main bonding clamp on a gas pipe with a wander lead, you read 0.05 Ω at the clamp terminal and 1.6 Ω on the pipe 0.75 m beyond the clamp. What does this show?

Show answer

Answer: A. Poor contact between the clamp and the pipe

  • GN3 compares the resistance to the clamp terminal with the resistance to the pipe itself about 0.5 m to 1 m away.
  • The readings should be roughly the same if the clamp connects well.
  • A big jump shows corrosion, paint or a loose clamp.

Clean the pipe, refit the clamp and retest.

Why the others are wrong:

B: the 0.05 Ω reading at the clamp terminal shows the conductor is continuous.

C: the two readings should be roughly the same if the clamp makes good contact.

D: the reading is taken close to the clamp, so the clamp contact is the obvious cause.

Memory trick:

Clamp and pipe should read like twins.

Find it in the book

IET Guidance Note 3 (2022 edition), page 61

Reg 643.2.1

Q2. A motor contactor coil pulls in when the start button is pressed, but the motor does not run. Tests show no voltage on the load side of the main contacts. What fault is most likely?

Show answer

Answer: B. The main contacts are failing to close, giving an open circuit

  • The coil pulls in, so the control circuit and coil are working.
  • No voltage on the load side points to the main contacts.
  • Contacts that fail to close cause an open circuit fault.

Use each test result to rule out part of the circuit.

Why the others are wrong:

A: welded contacts would keep the load supplied, not cut it off.

C: the supply is missing on the load side of the contacts, before the motor.

D: the coil is pulling in, so it is energising.

The maths

Step 1: coil pulls in, so the coil and control circuit are healthy.
Step 2: no voltage after the contacts, so the break is at the contacts.
Step 3: contacts failing to close = open circuit.

Memory trick:

Coil works, no volts out: contacts open.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 321

Reg AC 3.5 Contacts

Q3. A circuit feeding a server room cannot be switched off. With a leakage clamp meter around its line and neutral only, you read 3.8 A. What does this indicate?

Show answer

Answer: B. A probable line or neutral to earth fault

  • Clamping live conductors only shows the current that is not returning through them, the 'earth leakage'.
  • A few mA usually means protective conductor currents.
  • Many amps may indicate a line-to-earth or neutral-to-earth fault.

This gives information on insulation where isolation is not possible.

Why the others are wrong:

A: normal protective conductor currents are a few milliamps, not several amps.

C: load current flows out on line and back on neutral, so it cancels in the clamp.

D: for this test the clamp goes round the live conductors only.

Memory trick:

Milliamps is normal, amps is a fault.

Find it in the book

IET Guidance Note 3 (2022 edition), page 185

Reg Appendix C

Q4. A landing lighting circuit with two-way switching passed its insulation test, yet the RCD now trips whenever the upstairs switch is in one position. What was most likely missed during the test?

Show answer

Answer: A. Switches were not tested in every position

  • With two-way and intermediate switching, each strapper is only in circuit in certain switch positions.
  • GN3 requires the switches to be operated one at a time and the insulation test repeated in each configuration.

A damaged strapper can hide in the position that was never tested.

Why the others are wrong:

B: 1000 V is for circuits above 500 V and would not find a strapper fault better.

C: continuity would not reveal insulation damage on one strapper.

D: removing lamps is correct procedure for an insulation test.

Memory trick:

Flip every switch or miss a strapper.

Find it in the book

IET Guidance Note 3 (2022 edition), page 70

Reg 643.3

Q5. A machine is reported as faulty but nothing wrong can be found. Which source would best show whether it is simply being operated in the wrong mode?

Show answer

Answer: D. The manufacturer's manual or user guide

  • Manufacturer's information such as manuals and user guides helps decide if equipment is faulty or just not operated correctly.

Sometimes the fault is the operator, not the machine.

Why the others are wrong:

A: waste records are not relevant to operating modes.

B: the EIC covers the installation, not how a machine is operated.

C: this gives cable data, not machine operation.

Memory trick:

Read the manual before blaming the machine.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 340

Reg AC 4.5 Information sources

Q6. A 40 m radial circuit in 2.5/1.5 mm² copper cable (19.51 mΩ/m for R1 + R2 at 20 °C) gives an (R1 + R2) reading of 2.40 Ω. What does this suggest?

Show answer

Answer: D. A poor joint, as about 0.78 Ω would be expected

  • Expected (R1 + R2) = length x mΩ/m / 1000.
  • 40 x 19.51 / 1000 = 0.78 Ω.
  • Healthy connections add very little, so 2.40 Ω points to a poor termination or joint.

Trace it with test method 2 or by testing at each point along the circuit.

Why the others are wrong:

A: this uses only the 2.5 mm² line value of 7.41 mΩ/m and ignores the cpc.

B: this does not match 40 x 19.51 mΩ, which gives under 1 Ω.

C: this mistakes milliohms per metre for a figure ten times too large.

The maths

R1 + R2 = (40 x 19.51) / 1000
= 780.4 / 1000
= 0.78 Ω expected
Measured 2.40 Ω is about three times higher, so look for a poor connection.

Memory trick:

Metres x milliohms, then / 1000.

Find it in the book

IET Guidance Note 3 (2022 edition), page 59

Reg 643.2.1

Want 114 more QELTK3/007 questions? Start a free timed mock.