Q1. Underfloor heating is laid on a ground floor. Downward heat loss should be limited to no more than:
Show answer
Answer: B. 10 W/m²
- Ground floors and floors in contact with the outside should be insulated to limit downward losses to no more than 10 W/m² (2026 para 5.35; 2021 para 6.29).
- Underfloor heating in screed floors over 65mm should also set back automatically.
Heat lost into the ground does not warm the room.
Why the others are wrong:
A: AD L sets 10 W/m², not 25.
C: AD L sets 10 W/m², not 50.
D: 1.25 is a thermal resistance in m²K/W, not a heat loss limit.
Memory trick:
Ground floor UFH: lose no more than 10.
Find it in the book
Approved Document L Vol 1 2021 (incl. 2023), page 46; 2026 edition, page 52