Part J Flues: Hearths, fireplaces, fuel storage and appliance-specific rules practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

27 of our 90 Part J Combustion Appliances and Flues (PART-J-FLUES) questions are on hearths, fireplaces, fuel storage and appliance-specific rules, about 30% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A prefabricated appliance chamber is being assembled for an open fire. What is the minimum thickness of the back section?

Show answer

Answer: B. 100mm

  • Table 4: base 50mm, sides 75mm, back 100mm, top slab/lintel/gather 100mm.
  • Components should be insulating concrete of density 1200 to 1700kg/m³.

The back takes the most direct heat from the fire.

Why the others are wrong:

A: 50mm is the minimum for the base.

C: 75mm is the minimum for the side sections.

D: 125mm is the thickness of a constructional hearth.

Memory trick:

Base 50, sides 75, back and top 100.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), pages 38 and 40

Reg Approved Document J (2010 incl. 2022 amendments), para 2.30 and Table 4

Q2. A 1200-litre domestic heating oil tank is planned 8m from a stream. What does Approved Document J indicate?

Show answer

Answer: D. Secondary containment is needed, as the tank is within 10m of inland freshwater

  • Significant pollution risk (so secondary containment) includes: total capacity over 2500 litres, within 10m of inland freshwaters or coastal waters, within 50m of potable sources, near open drains, vent not visible from the fill point, or in SPZ Zone 1.
  • Any one trigger is enough.

Inland freshwaters include ditches and field drains that feed streams.

Why the others are wrong:

A: capacity is only one trigger; being within 10m of a stream is another.

B: 50m applies to wells, boreholes and springs; streams have a 10m trigger.

C: the 3500 litre figure is the J7 scope limit, not the bund trigger.

Memory trick:

Ten metres from water, fifty from a well.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 64

Reg Approved Document J (2010 incl. 2022 amendments), para 5.8

Q3. A 9kW solid fuel stove with a flue draught stabiliser is fitted in an older house with air permeability above 5.0m³/(h.m²). What permanent vent area is needed?

Show answer

Answer: C. 4900mm²

  • Table 1, appliance with a draught stabiliser, permeability above 5.0: 300mm²/kW for the first 5kW, 850mm²/kW for the balance.
  • (5 x 300) + (4 x 850) = 1500 + 3400 = 4900mm².

The stabiliser draws room air into the flue, so more ventilation is needed.

Why the others are wrong:

A: this applies 850mm²/kW to all 9kW, the rule for tighter dwellings.

B: this applies 300mm²/kW to all 9kW instead of just the first 5kW.

D: this uses the no-stabiliser rule of 550mm²/kW above 5kW.

The maths

First 5kW: 5 x 300 = 1500mm²
Balance 4kW: 4 x 850 = 3400mm²
Total = 4900mm² (49cm²)

Memory trick:

Stabiliser: 300 for five, 850 for the rest.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 29

Reg Approved Document J (2010 incl. 2022 amendments), Table 1 and Note 3

Q4. What is the smallest room or space volume in which a flueless instantaneous gas water heater should be installed?

Show answer

Answer: A. 5m³

  • A flueless instantaneous water heater should not be installed in a room or space under 5m³.
  • Diagram 33: max 11kW (net); vents of 10,000mm² (5 to 10m³), 5000mm² (10 to 20m³), none over 20m³.

Products go straight into the room air, so small rooms are unsafe.

Why the others are wrong:

B: 10m³ is a band boundary in the Diagram 33 vent table, not the minimum volume.

C: over 20m³ means no permanent vent is needed; it is not the minimum.

D: this is smaller than the 5m³ minimum.

Memory trick:

Flueless water heater: five cubes minimum.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 45

Reg Approved Document J (2010 incl. 2022 amendments), para 3.9

Q5. LPG cylinders are being sited against a house wall. How far must the cylinder valves be from a flue terminal or openable window?

Show answer

Answer: A. At least 1m horizontally and 300mm vertically

  • Cylinder valves: at least 1m horizontally and 300mm vertically from openings and heat sources such as flue terminals.
  • At least 2m from untrapped drains or cellar hatches, unless a wall at least 250mm high intervenes.
  • Base: concrete at least 50mm thick or slabs on mortar.

LPG is heavier than air and pools at low level.

Why the others are wrong:

B: 2m is the distance from untrapped drains, unsealed gullies or cellar hatches.

C: the figures are the other way round.

D: 2.5m is a Table 11 separation for small bulk tanks.

Memory trick:

Cylinders: 1 across, 0.3 up from openings.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), pages 65 and 67

Reg Approved Document J (2010 incl. 2022 amendments), para 5.20 and Diagram 44

Q6. An open-flued oil boiler of 18kW rated output, with no draught break, is installed in a utility room of a 1970s house with air permeability above 5.0m³/(h.m²). What permanent vent area is needed?

Show answer

Answer: A. 7150mm²

  • Diagram 40, vent A: 550mm² per kW output for an open-flued oil appliance in a room.
  • Note 5: in older dwellings above 5.0m³/h/m², the first 5kW can be ignored.
  • (18 - 5) x 550 = 7150mm² (71.5cm²).

A draught break would add a further 550mm²/kW.

Why the others are wrong:

B: this uses the full 18kW without ignoring the first 5kW allowed in older dwellings.

C: this uses the gas rate of 500mm²/kW instead of 550mm²/kW for oil.

D: this uses 1100mm²/kW, the compartment rate, instead of 550mm²/kW.

The maths

Ignore first 5kW: 18 - 5 = 13kW
13 x 550mm²/kW = 7150mm²
7150 / 100 = 71.5cm²

Memory trick:

Oil room vent: 550 a kW, first five free if leaky.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), pages 57 and 72

Reg Approved Document J (2010 incl. 2022 amendments), Diagram 40, Note 5 and Appendix D

Want 84 more Part J Flues questions? Start a free timed mock.

Start a free mock

Full mock, no card needed. Full workouts on the first 5 questions.

Other Part J Flues topics

Free official guides for this topic

Our questions are written from these documents. Download them free to revise from the source.

© Crown copyright (GOV.UK). Unchanged copies, reproduced under the Open Government Licence v3.0. FreeMocks is not connected to or endorsed by HSE or the government.

Revise this topic