30 of our 90 Part J Combustion Appliances and Flues (PART-J-FLUES) questions are on flues, chimneys and terminals, about 33% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Which statement about the coring ball test is correct?

Show answer

Answer: A. It should be done before smoke testing and not used in flexible metal liners

  • The coring ball test proves the minimum diameter of circular flues and checks for obstructions.
  • It should be done before smoke testing, is not applicable to fluepipes and should not be used with flexible metal liners.

A coring ball can seriously damage a flexible metal liner.

Why the others are wrong:

B: it checks for obstruction, not gas-tightness, and is not for fluepipes.

C: a ball will not detect obstructions in the corners of square flues.

D: flue tests are not a substitute for appliance spillage tests.

Memory trick:

Ball first, smoke second, never down a flexi.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 74

Reg Approved Document J (2010 incl. 2022 amendments), Appendix E, para E9

Q2. The expected flue gas temperature of an older oil appliance cannot be found from the maker or OFTEC. How should the flue be designed?

Show answer

Answer: C. For a flue gas temperature greater than 250°C

  • Modern CE-marked boilers normally run at or below 250°C; condensing appliances well below 100°C.
  • Where information is not available, construct the flue for an assumed temperature greater than 250°C.

This leads to the Section 1 and 2 masonry or metal chimney guidance.

Why the others are wrong:

A: below 100°C is typical of condensing appliances, not a safe default.

B: without information, AD J says assume the higher figure.

D: AD J gives no middle default; it says assume over 250°C.

Memory trick:

Don't know? Assume over 250.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 59

Reg Approved Document J (2010 incl. 2022 amendments), para 4.10

Q3. A 12kW closed stove will burn only smokeless fuel. What is the minimum flue diameter in the chimney?

Show answer

Answer: A. 125mm

  • Table 2: closed appliance up to 20kW burning smokeless or low-volatiles fuel: 125mm diameter.
  • Square or rectangular flues need the same area, with a minimum dimension of 100mm (straight) or 125mm (with bends or offsets).

The flue must also be no smaller than the appliance outlet or the maker's recommendation.

Why the others are wrong:

B: 150mm is for other closed appliances up to 30kW burning any fuel.

C: 175mm is for closed appliances above 30kW and up to 50kW.

D: 200mm is for open fireplaces up to 500mm x 550mm.

Memory trick:

Small and smokeless: 125.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 30

Reg Approved Document J (2010 incl. 2022 amendments), Table 2

Q4. A natural draught open-flued gas appliance has a 150mm diameter flue. What does Approved Document J say about the flue outlet?

Show answer

Answer: B. It should be fitted with an outlet terminal

  • Flues for natural draught open-flued gas appliances should have outlet terminals if the flue is no greater than 170mm diameter.
  • Above 170mm, assess blockage risk; a cage with 6mm to 25mm mesh and free area at least twice the flue area may suit.

Terminals keep out birds, leaves and rain.

Why the others are wrong:

A: it is the other way round: terminals are needed up to 170mm.

C: flues up to 170mm should have an outlet terminal.

D: spark arrestors are not generally recommended and are a solid fuel topic.

Memory trick:

Up to 170, fit a terminal.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 51

Reg Approved Document J (2010 incl. 2022 amendments), para 3.25

Q5. A new open fireplace has a finished opening of 480mm x 540mm. What is the minimum flue size?

Show answer

Answer: B. 200mm diameter, or a rectangular flue of equal area with no side under 175mm

  • Table 2: fireplace with an opening up to 500mm x 550mm: 200mm diameter or square/rectangular of the same area with a minimum dimension of 175mm.
  • Bigger openings use the 15 per cent rule.

It is the finished opening, after linings and surrounds, that counts.

Why the others are wrong:

A: 175mm diameter is for closed appliances above 30kW and up to 50kW; an open fire of this size needs 200mm.

C: 150mm is for other closed appliances up to 30kW; an open fire of this size needs 200mm.

D: 125mm is for small closed appliances or pellet appliances.

Memory trick:

Open fire: 200 round, 175 minimum side.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 30

Reg Approved Document J (2010 incl. 2022 amendments), Table 2

Q6. A solid fuel flue outlet will be 400mm horizontally from the ridge of a pitched roof. How high should it be?

Show answer

Answer: B. At least 600mm above the ridge

  • Diagram 17, position A: outlet at or within 600mm of the ridge should be at least 600mm above the ridge.
  • Further down the roof, position B rules apply instead.

The ridge zone has turbulent air, so the outlet needs to clear it well.

Why the others are wrong:

A: 1000mm relates to the roof intersection or the top of an opening, not the ridge zone.

C: being as high as the ridge is an option for outlets elsewhere on the roof, not within 600mm of it.

D: 300mm is less than the 600mm Diagram 17 sets.

Memory trick:

Near the ridge, 600 over it.

Find it in the book

Approved Document J (2010 incl. 2022 amendments), page 31

Reg Approved Document J (2010 incl. 2022 amendments), Diagram 17 (A)

Want 84 more Part J Flues questions? Start a free timed mock.

Start a free mock