Q1. A designer proposes two non-self-resetting energy cut-outs on a large unvented store, both wired to the same motorised valve and fed from a shared temperature sensor. Is this acceptable?
Show answer
Answer: D. No, each cut-out should have its own valve and sensor
- 3.32: where there is more than one energy cut-out, each should be independent.
- The guidance gives the example of each having a separate motorised valve and a separate temperature sensor.
A single valve or sensor failure must not disable both levels of protection.
Why the others are wrong:
A: the guidance gives separate sensors as part of independence too, not just separate valves.
B: matching settings does not make them independent; a shared valve or sensor is a common point of failure.
C: the relief valve does not remove the need for each cut-out to be independent.
Memory trick:
Independent means nothing shared: own sensor, own valve.