G3 Unvented: Unvented systems and safety devices practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

19 of our 60 Unvented Hot Water Storage Systems (G3) (G3-UNVENTED) questions are on unvented systems and safety devices, about 32% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A designer proposes two non-self-resetting energy cut-outs on a large unvented store, both wired to the same motorised valve and fed from a shared temperature sensor. Is this acceptable?

Show answer

Answer: D. No, each cut-out should have its own valve and sensor

  • 3.32: where there is more than one energy cut-out, each should be independent.
  • The guidance gives the example of each having a separate motorised valve and a separate temperature sensor.

A single valve or sensor failure must not disable both levels of protection.

Why the others are wrong:

A: the guidance gives separate sensors as part of independence too, not just separate valves.

B: matching settings does not make them independent; a shared valve or sensor is a common point of failure.

C: the relief valve does not remove the need for each cut-out to be independent.

Memory trick:

Independent means nothing shared: own sensor, own valve.

Reg Approved Document G, 3.32

Q2. An unvented primary thermal store has no means of automatically refilling the stored water. The designer wants to fit a temperature relief valve as the second safety device. What does Approved Document G say?

Show answer

Answer: A. Omit the relief valve and fit a second independent cut-out

  • 3.35: temperature relief valves and combined T&P relief valves should not be used where there is no provision to automatically replenish the stored water (e.g. unvented primary thermal stores).
  • Instead, fit a second non-self-resetting energy cut-out, independent of the one under 3.18(a).

A relief valve discharging from a store that cannot refill would leave it boiling dry.

Why the others are wrong:

B: combined T&P valves are also excluded where the stored water cannot be replenished.

C: the guidance deals with this case by excluding relief valves, not by adding a filling loop.

D: the stated alternative is a second independent cut-out, not an alarm.

Memory trick:

Can't refill? Don't spill: use a second cut-out.

Reg Approved Document G, 3.35

Q3. A developer is building a new detached house. What is the maximum temperature of hot water that may be delivered to the fixed bath?

Show answer

Answer: D. 48°C

  • Requirement G3(4): the hot supply to any fixed bath must not be able to deliver water above 48°C.
  • Paragraph 3.65: achieved with an in-line blending valve or other temperature control device with a maximum temperature stop and suitable pipework.

This applies to new dwellings and those formed by certain material changes of use.

Why the others are wrong:

A: 60°C is the cap on water leaving a high-temperature store, not the bath outlet limit.

B: 43°C is a common figure people quote for showers and care settings, but G3(4) sets the bath limit higher.

C: 50°C is close but above the limit set by requirement G3(4).

Memory trick:

Bath: 4 8, "for eight" degrees above 40.

Reg Approved Document G, Requirement G3(4) and 3.65

Q4. An unvented cylinder is heated by a boiler coil, a solar thermal coil and an electric immersion heater. How many separate non-self-resetting energy cut-outs does Approved Document G expect?

Show answer

Answer: C. Three, one for each heat source

  • 3.33: where an energy cut-out is fitted under 3.13(a) or 3.18, each heat source should have a separate non-self-resetting energy cut-out.
  • Here there are three heat sources: boiler coil, solar coil and immersion heater, so three cut-outs.

If only one source was cut off, the others could carry on heating the stored water.

Why the others are wrong:

A: the boiler and solar coils are separate heat sources and each needs its own cut-out.

B: each heat source needs its own cut-out so any one source can be stopped.

D: neither the solar coil nor the immersion is exempt from having its own cut-out.

Memory trick:

Count the heat sources, count the cut-outs.

Reg Approved Document G, 3.33

Q5. An unvented cylinder has lost its hot water and the homeowner finds the overheat cut-out on the immersion heater has operated. How is this device designed to be reset?

Show answer

Answer: C. Only by hand, once someone has reset it manually

  • AD G defines a non-self-resetting energy cut-out as a device that interrupts the heat supply when a fixed (factory set) temperature is exceeded.
  • Once it has operated it should only be possible to reset it manually.

This forces someone to investigate why the thermostat failed rather than letting the system cycle back into an overheat.

Why the others are wrong:

A: cycling the power must not restore heating; manual intervention at the device is needed.

B: that describes a self-resetting device; the required cut-out must not reset itself.

D: the relief valve is a separate device and has no role in resetting the cut-out.

Memory trick:

Non-self-resetting: it waits for a person, not for the water to cool.

Reg Approved Document G, Key terms: non-self-resetting energy cut-out

Q6. A plumber plans to build a 250 litre, 24kW unvented system from a plain cylinder plus separately bought valves, cut-outs and an expansion vessel. What does Approved Document G expect for a system of this size?

Show answer

Answer: C. A proprietary hot water storage system unit or package

  • 3.22: unvented systems up to 500 litres and less than 45kW should be in the form of a proprietary hot water storage system unit or package.
  • The package should satisfy an appropriate standard (e.g. BS EN 12897) so that G3(2) and G3(3) are met.

Assembling a system from loose components does not give that product-level assurance.

Why the others are wrong:

A: for systems this size the guidance expects a proprietary unit or package, not loose parts.

B: bespoke engineered designs are for systems over 500 litres.

D: being under 45kW and 500 litres is exactly what puts it in the unit or package category.

Memory trick:

Domestic size (500 L, under 45kW): buy it as a unit or package.

Reg Approved Document G, 3.22

Want 54 more G3 Unvented questions? Start a free timed mock.