Q1. A customer complains of dim lights. You measure 214 V at the origin of a 230 V single-phase supply. Is this within the supply tolerance described in the book?
Show answer
Answer: C. No, the lower limit is about 216 V
- Lower limit = 230 V less 6%.
- 230 x 0.94 = 216.2 V, so 214 V is too low.
A reading below the tolerance is a supply issue to raise with the distributor.
Why the others are wrong:
A: 207 V is a 10% reduction, but the lower tolerance is 6%.
B: there is a defined lower limit well above 200 V.
D: 225 V is not the result of applying the -6% tolerance.
The maths
Lower limit = 230 x (1 - 0.06) = 230 x 0.94 = 216.2 V
Measured 214 V < 216.2 V, so it is outside tolerance.
Memory trick:
230 minus 6% is 216: below that, call the DNO.
Find it in the book
Linsley, Electrical Installation Work Level 3 (EAL Edition), page 121