ELEC3/04a: Design calculations practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

80 of our 240 Installation Planning, Preparing and Designing (ELEC3-04A) questions are on design calculations, about 33% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Regulations that come up most

The regulation groups our design calculations questions test most often. Know where these are in your book before the exam.

  • 525 · 5 questions
  • 411.4 · 4 questions
  • 433.1 · 4 questions
  • 543.1 · 4 questions
  • 411.5 · 2 questions
  • 411.3 · 1 questions
  • 411.8 · 1 questions

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A customer complains of dim lights. You measure 214 V at the origin of a 230 V single-phase supply. Is this within the supply tolerance described in the book?

Show answer

Answer: C. No, the lower limit is about 216 V

  • Lower limit = 230 V less 6%.
  • 230 x 0.94 = 216.2 V, so 214 V is too low.

A reading below the tolerance is a supply issue to raise with the distributor.

Why the others are wrong:

A: 207 V is a 10% reduction, but the lower tolerance is 6%.

B: there is a defined lower limit well above 200 V.

D: 225 V is not the result of applying the -6% tolerance.

The maths

Lower limit = 230 x (1 - 0.06) = 230 x 0.94 = 216.2 V
Measured 214 V < 216.2 V, so it is outside tolerance.

Memory trick:

230 minus 6% is 216: below that, call the DNO.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 121

Reg ESQCR 2002

Q2. A conduit 6 m long with one bend will carry three 2.5 mm² cables and one 4.0 mm² CPC. Cable factors are 30 (2.5 mm²) and 43 (4.0 mm²). Conduit factors for the run are 143 (16 mm) and 233 (20 mm). What is the minimum conduit size?

Show answer

Answer: D. 16 mm

  • Cable sum = (3 x 30) + (1 x 43) = 133
  • 16 mm conduit factor = 143, which is at least 133

Include the CPC in the cable factor sum, then choose the smallest conduit whose factor is equal to or greater than that sum.

Why the others are wrong:

A: 20 mm would work but 16 mm already has enough capacity, so it is not the minimum.

B: this is far larger than needed for a cable sum of 133.

C: the 16 mm factor of 143 already exceeds the cable sum of 133.

The maths

Sum = (3 x 30) + 43 = 90 + 43 = 133
16 mm factor 143 >= 133, so 16 mm is suitable

Memory trick:

Don't forget the CPC: it takes up space too.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 166

Reg OSG Appendix E

Q3. When assessing current demand, how does the On-Site Guide treat small loads such as an electric clock, shaver supply unit or bell transformer?

Show answer

Answer: D. They may be neglected

  • Clocks, shaver supply units and bell transformers draw very little current.
  • They may be neglected in the demand assessment.

A 2 A socket outlet, by contrast, is taken as 0.5 A.

Why the others are wrong:

A: they are small enough to be ignored.

B: 100 W applies to lighting points.

C: the 1.8 factor applies to discharge lighting.

Memory trick:

Tiny loads, no maths.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 220

Reg OSG App A (Table A1)

Q4. Why may a ring final circuit wired in 2.5 mm2 thermoplastic cable be protected by a 32 A device when the cable alone is rated lower?

Show answer

Answer: A. The load current shares between the two legs of the ring

  • In a ring the current splits between both legs.
  • This makes 2.5 mm2 acceptable on a 30 A or 32 A device.

The designer should still aim for reasonable load sharing in each leg.

Why the others are wrong:

B: a 32 A device does not trip at 20 A.

C: plugs can be fused at up to 13 A.

D: the cable rating is not changed by the ring layout.

Memory trick:

Two roads to the socket share the traffic.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 130

Reg On-Site Guide Appendix H

Q5. A 9.2 kW electric shower is supplied at 230 V. What is its design current Ib?

Show answer

Answer: D. 40 A

  • For a resistive load, power factor = 1, so I = P / V.
  • 9200 / 230 = 40 A.

Showers take their full rated current with no diversity within the circuit.

Why the others are wrong:

A: this divides by 2300 instead of 230.

B: this divides by 400 V, the three-phase voltage, instead of 230 V.

C: this adds 15% that is not part of the calculation.

The maths

Ib = P / (V x cos phi)
Ib = 9200 / (230 x 1)
Ib = 40 A

Memory trick:

Watts divided by 230 gives amps.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 220

Reg OSG App A

Q6. A Type B circuit-breaker to BS EN 60898 is rated at 40 A. Using the multiple at which a Type B device trips instantly (5 x In), what current is needed to ensure instantaneous disconnection?

Show answer

Answer: A. 200 A

  • Type B trips instantly between 3 and 5 x In
  • To be sure of instant tripping, use the top of the band: 5 x 40 = 200 A

The book's example of a 20 A Type B needing 100 A uses the same rule.

Why the others are wrong:

B: that is 3 x In, the bottom of the Type B band, which does not guarantee tripping.

C: that is 10 x In, the figure for a Type C device.

D: that is only 2 x In, an overload level.

The maths

Ia = 5 x In = 5 x 40 = 200 A

Memory trick:

B for 5, C for 10.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 205

Reg Table 3A, Appendix 3

Want 234 more ELEC3/04a questions? Start a free timed mock.