Q1. In a star-delta starter, to roughly what fraction of the running voltage is each winding's voltage reduced during starting?
Show answer
Answer: C. About 58%
- In star, each winding gets VL / root 3 instead of VL
- 1 / 1.732 = 0.577, about 58%
- 400 V becomes about 231 V per winding
This reduces both the starting current and the starting torque.
Why the others are wrong:
A: one third is the line current ratio, not the voltage ratio.
B: the factor is 1 divided by root 3, not one half.
D: this is the reduction from cos 30, which does not apply.
The maths
400 / 1.732 = 231 V
231 / 400 = 0.58 = 58%
Memory trick:
One over root 3 = 58%.
Find it in the book
Linsley, Electrical Installation Work Level 3 (EAL Edition), page 465