Q1. In a star-delta starter, to roughly what fraction of the running voltage is each winding's voltage reduced during starting?

Show answer

Answer: C. About 58%

  • In star, each winding gets VL / root 3 instead of VL
  • 1 / 1.732 = 0.577, about 58%
  • 400 V becomes about 231 V per winding

This reduces both the starting current and the starting torque.

Why the others are wrong:

A: one third is the line current ratio, not the voltage ratio.

B: the factor is 1 divided by root 3, not one half.

D: this is the reduction from cos 30, which does not apply.

The maths

400 / 1.732 = 231 V
231 / 400 = 0.58 = 58%

Memory trick:

One over root 3 = 58%.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 465

Reg AC 5.8

Q2. What is the synchronous speed of a six-pole machine on a 50 Hz supply?

Show answer

Answer: B. 1000 rpm

  • ns = f / p, where p is the number of pole pairs
  • Six poles = 3 pole pairs: 50 / 3 = 16.67 rev/s
  • × 60 = 1000 rpm

Always convert poles to pole pairs first.

Why the others are wrong:

A: this uses six pole pairs instead of three.

C: this treats the machine as two-pole.

D: this is the speed in revolutions per second, not per minute.

The maths

p = 6 / 2 = 3
ns = 50 / 3 = 16.67 rev/s
16.67 x 60 = 1000 rpm

Memory trick:

Poles ÷ 2 first, then f ÷ p, then × 60.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 459

Reg AC 5.6

Q3. A cage induction motor's starting torque is less than the torque needed by its load. Which is NOT a way to overcome this, according to the textbook?

Show answer

Answer: C. Fit a larger capacitor across the supply

  • Three methods: match the motor to the load, connect the load after run-up, or add rotor resistance to a wound rotor
  • A capacitor across the supply corrects power factor, not starting torque

A machine whose starting torque is below the load torque will not start.

Why the others are wrong:

A: matching the motor to the load is one of the three methods.

B: this is one of the three methods.

D: this is one of the three methods.

Memory trick:

Match it, unload it, or resist it.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 466

Reg AC 5.7

Q4. A shaded pole motor is suitable only for very small machines. What approximate maximum rating is given?

Show answer

Answer: B. About 50 W

  • Shaded pole motors are simple and robust, for ratings below about 50 W
  • A copper or brass shading ring shifts the field to create rotation
  • Very low starting torque: oven fans, turntables, fan heaters

Reversing usually means turning the whole motor round.

Why the others are wrong:

A: this is too large for a shaded pole motor.

C: this is the d.o.l. starter limit.

D: this is the stated motor starter threshold.

Memory trick:

Shaded pole: small fan, about 50 W.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 463

Reg AC 5.7

Q5. A d.c. motor armature has 200 active conductors, each 0.15 m long in a 0.6 T field and each carrying 4 A. What is the total force on the conductors?

Show answer

Answer: A. 72 N

  • Force on one conductor: F = BIl = 0.6 × 4 × 0.15 = 0.36 N
  • 200 conductors: 0.36 × 200 = 72 N

Force depends on flux density, current and active length, which is why armatures carry many conductors.

Why the others are wrong:

B: that is the force on a single conductor only.

C: that leaves out the flux density of 0.6 T.

D: that leaves out the 4 A current.

The maths

One conductor: F = 0.6 × 4 × 0.15 = 0.36 N
Total: 0.36 × 200 = 72 N

Memory trick:

F = BIL: think 'Bil-l', flux times current times length.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 455

Reg Force on a conductor (F = BIl)

Q6. Why are the bars of a cage rotor often slightly skewed?

Show answer

Answer: B. To give better starting and quieter running

  • A cage rotor has copper or aluminium bars short-circuited at each end
  • Skewing the bars gives better starting and quieter running
  • It needs no slip rings or brushes, so it is very robust

Its main drawback is low starting torque.

Why the others are wrong:

A: a cage rotor needs no brushes.

C: speed depends on frequency and poles.

D: that requires a wound rotor and slip rings.

Memory trick:

Skewed bars, smooth start.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 460

Reg AC 5.6

Want 264 more ELEC3/008 questions? Start a free timed mock.