ELEC3/008: DC and AC circuit principles practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

98 of our 270 Principles of Electrical Science (ELEC3-008) questions are on dc and ac circuit principles, about 36% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. Three 40 ohm resistive elements are connected in delta to a 400 V three-phase supply. What is the line current?

Show answer

Answer: A. 17.3 A

  • In delta, VL = Vp = 400 V
  • Ip = 400 / 40 = 10 A
  • IL = root 3 × Ip = 1.732 × 10 = 17.3 A

Delta keeps the voltage the same but multiplies the current by root 3.

Why the others are wrong:

B: this is the phase current; in delta the line current is root 3 times larger.

C: this treats the load as star connected.

D: this multiplies the phase current by 3 instead of root 3.

The maths

Vp = VL = 400 V
Ip = 400 / 40 = 10 A
IL = 1.732 x 10 = 17.3 A

Memory trick:

Delta: volts the same, amps times root 3.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 430

Reg AC 3.9

Q2. A 4 Ω resistor is connected in series with a parallel pair of 10 Ω and 15 Ω across a 50 V d.c. supply. What voltage appears across the parallel pair?

Show answer

Answer: B. 30 V

  • Parallel pair: (10 × 15)/(10 + 15) = 6 Ω
  • Total resistance: 4 + 6 = 10 Ω, so I = 50/10 = 5 A
  • Voltage across the pair: 5 A × 6 Ω = 30 V

Reduce the parallel group to one equivalent resistor first, then treat the circuit as a simple series circuit.

Why the others are wrong:

A: that is the voltage across the 4 Ω series resistor, not the parallel pair.

C: the series resistor drops part of the supply, so the pair cannot receive the full 50 V.

D: that comes from adding 10 Ω and 15 Ω as if they were in series.

The maths

Rp = (10 × 15)/(10 + 15) = 150/25 = 6 Ω
Rt = 4 + 6 = 10 Ω
I = 50/10 = 5 A
Vp = 5 × 6 = 30 V (and 5 × 4 = 20 V across the 4 Ω, total 50 V)

Memory trick:

Collapse the parallel bit first, then share the volts in proportion to resistance.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 409

Reg Series and parallel combinations

Q3. A three-phase 400 V motor delivers 15 kW output at 85% efficiency and a power factor of 0.8. What is the line current?

Show answer

Answer: D. 31.8 A

  • Input power = 15 / 0.85 = 17.65 kW
  • I = P / (root 3 × V × cos phi) = 17,647 / (1.732 × 400 × 0.8)
  • I = 31.8 A

Always work out the electrical input first, because the supply provides the input, not the shaft output.

Why the others are wrong:

A: this uses the output power and ignores the efficiency.

B: this ignores the power factor.

C: this leaves out root 3.

The maths

Input = 15,000 / 0.85 = 17,647 W
I = 17,647 / (1.732 x 400 x 0.8)
= 17,647 / 554.2 = 31.8 A

Memory trick:

Shaft kW to supply kW first (÷ efficiency), then to amps.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 458

Reg AC 3.9

Q4. A coil with a resistance of 40 Ω and an inductive reactance of 30 Ω is connected to a 230 V a.c. supply. What true power does it consume?

Show answer

Answer: A. 846 W

  • Z = √(40² + 30²) = 50 Ω, so I = 230/50 = 4.6 A
  • Only resistance consumes power: P = I²R = 4.6² × 40 = 846 W
  • Check: P = VI cos φ = 230 × 4.6 × (40/50) = 846 W

The inductance stores and returns energy each cycle, so it uses no average power.

Why the others are wrong:

B: 230 × 4.6 is the apparent power in VA, not the true power.

C: I²XL gives the reactive power, which is not consumed.

D: V²/R ignores the reactance, so it overstates the current.

The maths

Z = √(40² + 30²) = 50 Ω
I = 230 / 50 = 4.6 A
P = I²R = 4.6² × 40 = 21.16 × 40 = 846.4 W
Check: pf = R/Z = 0.8, P = 230 × 4.6 × 0.8 = 846.4 W

Memory trick:

Only the R burns watts; the X just borrows and gives back.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 423

Reg Power in a.c. circuits

Q5. An 11 kV distribution network is star connected at the transformer. What is the voltage from each line to the star point?

Show answer

Answer: C. 6.35 kV

  • In star, Vp = VL / root 3
  • Vp = 11,000 / 1.732 = 6,350 V = 6.35 kV

The same rule applies at any voltage level.

Why the others are wrong:

A: line to star point voltage equals the line voltage only in delta.

B: this multiplies by root 3 instead of dividing.

D: this divides by 3 instead of root 3.

The maths

Vp = 11,000 / 1.732 = 6,351 V, about 6.35 kV

Memory trick:

Star: phase volts = line volts ÷ 1.732.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 427

Reg AC 3.9

Q6. A choke connected to 230 V a.c. draws 2 A. Ignoring its resistance, what is its inductive reactance?

Show answer

Answer: C. 115 Ω

  • Reactance can be found from XL = VL ÷ IL
  • 230 ÷ 2 = 115 Ω

Why the others are wrong:

A: multiplies voltage by current.

B: divides current by voltage.

D: subtracts the current from the voltage.

The maths

XL = V ÷ I = 230 ÷ 2 = 115 Ω

Memory trick:

Reactance is just Ohm's law with X instead of R.

Find it in the book

Linsley, Electrical Installation Work Level 3 (EAL Edition), page 416

Reg ELEC3/008 AC3.1 reactance

Want 264 more ELEC3/008 questions? Start a free timed mock.