Q1. Three 40 ohm resistive elements are connected in delta to a 400 V three-phase supply. What is the line current?
Show answer
Answer: A. 17.3 A
- In delta, VL = Vp = 400 V
- Ip = 400 / 40 = 10 A
- IL = root 3 × Ip = 1.732 × 10 = 17.3 A
Delta keeps the voltage the same but multiplies the current by root 3.
Why the others are wrong:
B: this is the phase current; in delta the line current is root 3 times larger.
C: this treats the load as star connected.
D: this multiplies the phase current by 3 instead of root 3.
The maths
Vp = VL = 400 V
Ip = 400 / 40 = 10 A
IL = 1.732 x 10 = 17.3 A
Memory trick:
Delta: volts the same, amps times root 3.
Find it in the book
Linsley, Electrical Installation Work Level 3 (EAL Edition), page 430