Heat Pumps L3: Installation and commissioning practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

20 of our 60 Heat Pump Systems Installation and Maintenance (Level 3) (HEAT-PUMP-L3) questions are on installation and commissioning, about 33% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. After the existing radiator circuit has been flushed and cleaned during a heat pump retrofit, which other items does the example commissioning checklist ask you to record for the heating system?

Show answer

Answer: A. Cleaner used, strainers or filters clear, and water treated

  • The central heating section includes:
    • HTG system flushed and cleaned, and cleaner used
    • Strainers/filters clear
    • HTG system water treated, and inhibitor/antifreeze used
    • system purged of air

Old systems hold sludge that will quickly block a heat pump's plate heat exchanger and filters if it is not removed.

Why the others are wrong:

B: these are boiler commissioning checks, not heat pump heating circuit items.

C: refractometer checks apply to ground loop antifreeze, not the radiator circuit.

D: this is not a measurement on the checklist.

Memory trick:

Clean it, check the strainer, dose it.

Reg MIS 3005-I:2025 Appendix A

Q2. To what minimum temperature must antifreeze in a ground array transfer fluid protect against freezing?

Show answer

Answer: D. -10°C

  • Sufficient antifreeze is added to protect the ground array fluid to at least -10°C.
  • Type and quantity must also suit the design flow rate, fluid viscosity and circulation pump.
  • Refractometer samples later confirm the level reached.

Ground loop return temperatures can fall below 0°C in normal operation, so plain water is never acceptable.

Why the others are wrong:

A: this gives no frost protection at all, as plain water freezes at 0°C.

B: not enough; the standard requires protection to a lower temperature.

C: stricter than required; designers may choose it, but the minimum is less onerous.

Memory trick:

Ground loop? Minus ten, minimum.

Reg MIS 3005-I:2025 4.1.2(e)

Q3. Two random samples of a commissioned ground loop fluid are checked with a refractometer. One shows freeze protection to -12°C and the other to -7°C. What should happen?

Show answer

Answer: B. Treat it as a fail, correct the mix and retest

  • Two separate, random samples are tested with a refractometer.
  • They should confirm protection to at least -10°C.
  • Evidence that this has been achieved should be given to the customer.

A low reading suggests poor mixing or not enough antifreeze, so the fluid needs correcting and rechecking.

Why the others are wrong:

A: both samples must confirm at least -10°C; averaging hides an under-protected part of the system.

C: the second sample shows the fluid is not protected everywhere to the required level.

D: the standard expects two samples to confirm protection and evidence to be given to the customer.

Memory trick:

Two samples, both minus ten or better.

Reg MIS 3005-I:2025 4.1.2(g)

Q4. An air source heat pump is to go in a narrow side passage, boxed in by a high wall and a fence. Which performance problem does the standard's note on siting specifically warn about?

Show answer

Answer: D. Cold exhaust air being drawn back into the unit

  • Heat pumps should be located to the manufacturer's instructions.
  • For air source units this includes factors that harm performance, such as recirculation of chilled air.
  • Recording the actual clearances around the unit is part of the example commissioning checklist.

If cold exhaust air is drawn back in, the evaporator works on colder air, so output and efficiency drop.

Why the others are wrong:

A: enclosing a unit tends to reflect noise, and the note concerns performance, not reduced sound.

B: frosting of insulation is not the siting issue the standard highlights.

C: water ingress is a product design matter, not the siting factor named in the note.

Memory trick:

Don't let it breathe its own cold breath.

Reg MIS 3005-I:2025 3.6.1

Q5. A ground source installer plans to raise the glycol concentration well above the design figure 'to be safe'. Which design factor does the standard specifically say the antifreeze quantity and type must suit?

Show answer

Answer: D. Fluid viscosity and the choice of circulation pump

  • Antifreeze quantity and type must be appropriate to the design, in particular:
    • the flow rate set by the heat pump manufacturer
    • the viscosity of the finished transfer fluid
    • the choice of ground array circulation pump

Too much glycol thickens the fluid, so the pump may not achieve the required flow rate and efficiency falls.

Why the others are wrong:

A: the cylinder is on the load side and has no bearing on ground array fluid.

B: colour is not a factor listed in the standard.

C: antifreeze in the ground array is a source-side matter, not linked to the emitter flow temperature.

Memory trick:

More glycol, thicker fluid, harder pump.

Reg MIS 3005-I:2025 4.1.2(e)

Q6. To reduce the effect of vibration on the building structure, what should be fitted to a heat pump in line with the manufacturer's instructions?

Show answer

Answer: C. Anti-vibration mounts and flexible hose connections

  • Anti-vibration pads, mats or mounts should be installed.
  • Flexible hose connections should be used on the pipework.
  • Both are fitted in accordance with the manufacturer's instructions.

These break the path for vibration from the unit into walls, floors and pipework.

Why the others are wrong:

A: modifying the casing is not what the standard asks for; mounts and flexible connections are.

B: rigid pipework carries vibration straight into the building.

D: pipe size affects flow and pressure drop, not vibration transfer.

Memory trick:

Soft feet, soft hoses.

Reg MIS 3005-I:2025 3.6.3