Heat Pumps L3: Heat pump system design practice questions

Written by Acacio Oliveira, founder of FreeMocks, plumbing and heating engineer (F-Gas registered).

30 of our 60 Heat Pump Systems Installation and Maintenance (Level 3) (HEAT-PUMP-L3) questions are on heat pump system design, about 50% of the bank. Try 6 below with full worked answers, then practise the rest in a timed mock.

Practice questions

Pick an answer to see why it's right, why the others are wrong, and the page in the book.

Q1. A living room in London has 14 m² of external wall with a U-value of 0.30 W/m²K. The designer uses column A (99%) of the MCS outside design temperatures. What is the heat loss through this wall?

Show answer

Answer: B. 95 W

  • Living room internal design temperature: 21 °C (Table 1)
  • London, column A (99%): -1.7 °C (Table 2)
  • Temperature difference = 21 - (-1.7) = 22.7 K
  • Heat loss = U x A x ΔT = 0.30 x 14 x 22.7 = 95.3 W

Always subtract a negative outside temperature carefully: it adds to the difference.

Why the others are wrong:

A: that uses an 18 °C room temperature; living rooms are designed at 21 °C.

C: that treats the London figure as +1.7 °C instead of -1.7 °C, giving 19.3 K.

D: that uses column B (-3.0 °C), but the designer chose column A.

The maths

ΔT = 21 - (-1.7) = 22.7 K
Q = 0.30 x 14 x 22.7 = 95.3 W, about 95 W

Memory trick:

Minus a minus is a plus: 21 + 1.7.

Reg MIS 3005-D 3.4.1(a), Tables 1 and 2

Q2. In an air to air heat pump design, which room counts as a habitable room and so must have an indoor unit?

Show answer

Answer: B. A dining room

  • Habitable room: used or intended for sleeping or living
  • Excluded: rooms with bath, shower or toilet facilities, rooms solely for cooking, service rooms, corridors and hallways, laundry and utility rooms
  • Any habitable room shall have an indoor unit

For non-habitable rooms, the designer should decide whether heating is needed and how it is provided.

Why the others are wrong:

A: rooms used solely for cooking are excluded from the definition.

C: utility rooms are listed as excluded service rooms.

D: rooms with toilet or bath facilities are excluded.

Memory trick:

Habitable = sleep or live in it.

Reg MIS 3005-D Section 2, 3.4.3(h)

Q3. A heat pump will heat a domestic hot water cylinder. What flow temperature must the heat pump be capable of at design conditions?

Show answer

Answer: B. At least 55 °C

  • When a heat pump serves a DHW cylinder, it shall be capable of a flow temperature of at least 55 °C at design conditions
  • Design conditions = the lowest temperature at which the heat pump meets the building's heat demand without a supplementary heater

This makes sure the heat pump can still heat water usefully on the coldest design day.

Why the others are wrong:

A: too low; the standard sets a minimum of 55 °C.

C: 60 °C is often linked to legionella control, but the MCS capability figure is 55 °C.

D: this is higher than the standard requires.

Memory trick:

Hot water heat pump: 55 or more on design day.

Reg MIS 3005-D 3.5.5

Q4. In the MCS simplified ground loop design method, what Reynolds number must the fluid flow in the active elements achieve at all times?

Show answer

Answer: B. 2,500 or more

  • The ground loop pipe and fluid must give a Reynolds number of at least 2,500 at all times
  • The look-up charts assume a Reynolds number above 2,500

Too slow a flow goes laminar and heat transfer from the ground drops off.

Why the others are wrong:

A: 2,500 is the figure the standard sets and the look-up charts assume.

C: higher than the standard requires.

D: that would be laminar flow, the opposite of what is wanted.

Memory trick:

Re 25 hundred: keep it turbulent.

Reg MIS 3005-D:2025 3.7.5(h)

Q5. A three-bedroom house is lived in by a couple with no children. Using the MCS method for domestic buildings, what daily hot water demand should the designer use?

Show answer

Answer: B. 180 litres per day

  • Daily demand Vd,average = 45 x N litres
  • N is the greater of (bedrooms + 1) and the number of known occupants
  • Here N = max(3 + 1, 2) = 4

The bedroom rule sets a floor on N, so a small household in a big house is still sized on bedrooms plus one.

Why the others are wrong:

A: that uses the two occupants, but N is the greater of occupants and bedrooms plus one, which here is 4.

C: that uses the bedroom count alone and leaves out the plus one.

D: that adds one person too many; N here is 4, not 5.

The maths

N = greater of (3 + 1 = 4) and 2 occupants = 4
Vd,average = 45 x 4 = 180 litres per day

Memory trick:

45 litres a head, heads = bedrooms + 1 unless more people actually live there.

Reg MIS 3005-D 3.5.2

Q6. When calculating heat loss through a suspended timber ground floor, which temperature difference does the MCS design standard require?

Show answer

Answer: D. Internal design temperature minus the design external air temperature

  • Suspended floor: ΔT = internal design room temperature (Table 1) minus design external air temperature (Table 2)
  • Solid floor on the ground: ΔT uses the local annual average external air temperature

A ventilated void under a suspended floor follows outside air, so it gets the full design temperature difference.

Why the others are wrong:

A: no halving is applied; the full design difference is used.

B: that is the rule for solid floors in contact with the ground, not suspended floors.

C: the standard gives no fixed ground figure for floors.

Memory trick:

Suspended floor hangs over outside air: use the design cold.

Reg MIS 3005-D 3.4.1(d)