Q1. A living room in London has 14 m² of external wall with a U-value of 0.30 W/m²K. The designer uses column A (99%) of the MCS outside design temperatures. What is the heat loss through this wall?
Show answer
Answer: B. 95 W
- Living room internal design temperature: 21 °C (Table 1)
- London, column A (99%): -1.7 °C (Table 2)
- Temperature difference = 21 - (-1.7) = 22.7 K
- Heat loss = U x A x ΔT = 0.30 x 14 x 22.7 = 95.3 W
Always subtract a negative outside temperature carefully: it adds to the difference.
Why the others are wrong:
A: that uses an 18 °C room temperature; living rooms are designed at 21 °C.
C: that treats the London figure as +1.7 °C instead of -1.7 °C, giving 19.3 K.
D: that uses column B (-3.0 °C), but the designer chose column A.
The maths
ΔT = 21 - (-1.7) = 22.7 K
Q = 0.30 x 14 x 22.7 = 95.3 W, about 95 W
Memory trick:
Minus a minus is a plus: 21 + 1.7.